background image

 

 

Technical Bulletin 

 

 

SuperDuct Signature Duct Smoke Detector 

 

6 to 10 duct widths

1 duct

width

Bend or other

obstruction

Airflow

 

• 

For detection of smoke in the supply air system, install 
the duct smoke detector in the supply air duct at a point 
downstream from the supply fan and air filters  

• 

For detection of smoke in the return air system, install the 
duct smoke detector in the return air duct at a point before 
the return air stream is diluted by outside air 

• 

Extend sampling tubes at least two-thirds across the width 
of the HVAC duct with the air inlet holes pointed into the 
direction of airflow  

• 

Support sampling tubes longer than 36 inches at the end 
farthest from the detector to avoid excessive vibration 

• 

Upon installation, perform an air pressure differential test 
to ensure the duct smoke detector is capable of sampling 
the air stream 

Installation sequence 

The steps required to install the duct smoke detector are 
described below. The order in which these steps are performed 
may vary depending installation requirements. 

1.  Verify the duct airflow direction and velocity. 

2.  Drill the mounting holes. 

3. Assemble 

the 

detector. 

4.  Mount the detector on the HVAC duct. 

5.  Verify the detector pressure differential. 

Installing the sampling tube from the front of 
the detector 

The sampling tube is normally installed from the rear, but it 
can also be installed from the front of the detector as shown in 
Figure 4. This method requires that you remove the detector 
cover. 

Note: 

Sampling tubes are ordered separately. 

Sampling tube

connector

Sampling tube

(fully assembled)

Detector

 

Figure 4: Sampling tube installed from the front 

Supporting sampling tubes greater than 36 
inches long 

NFPA requirements state that sampling tubes must extend at 
least two-thirds of the way into the duct and those that are 
greater than 36 inches long must be supported at both ends. To 
meet this requirement, drill a 3/4-inch hole on the opposite 
side of the duct. Extend the sampling tube through the hole as 
shown in Figure 5. Cut off the excess sampling tube and seal 
the opening around the tube with an approved sealant.  

Note: 

For ducts greater than or equal to 36 inches wide, use 

the next longest sampling tube available. 

HVAC

duct

Sampling

tube

Exhaust tube

Plug

Detector

Sealant

Airflow

   36 in

 

Figure 5: Installation with sampling tubes longer than the width 
of the duct 

Summary of Contents for 3100738

Page 1: ...e following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ventilating Systems UL 268A Smoke Detectors for Duct Applications...

Page 2: ...es are stored in nonvolatile memory This information can be retrieved and reviewed when desired Air is introduced to the duct smoke detector s sensing chamber through a sampling tube that extends into...

Page 3: ...rm red Power green Common alarm relay Unsupervised and power limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Operating voltage 15 2 to 19 95 Vdc Operating current Standby 45 A Alarm 4...

Page 4: ...ed when the amount of smoke in its sensing chamber exceeds its alarm threshold setting or when an alarm test is initiated Upon entering the alarm state the duct smoke detector s Alarm LED turns on Com...

Page 5: ...velocity 2 Drill the mounting holes 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube from the front of the detecto...

Page 6: ...ion for more than 5 seconds Using an SD TRM hold the SD MAG test magnet to the target area for more than 5 seconds Once activated verify the following The detector s Alarm LED is flashing If connected...

Page 7: ...oft bristle brush remove loose dirt and debris from inside the detector housing and cover Use isopropyl alcohol and a lint free cloth to remove dirt and other contaminants from the gasket on the detec...

Page 8: ...uct Signature Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 cm Figu...

Page 9: ...Active SIGA LED 1 Notes 1 No more than one remote test station or LED indicator can be connected to the detector at the same time Wiring is unsupervised Maximum wire resistance is 10 ohms per wire Pow...

Reviews: