SB4U Analog Audible Detector Base 
Installation Sheet 

EN  FR 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

EN: Installation Sheet 

Operation 

The SB4U Analog Audible Detector Base adds an audible 
output function to the listed compatible detectors. The base 
can operate as an independent local alarm, or as part of a 
zone or system alarm with synchronized audible output. 

The output of this detector base is field-configurable for output 
tone (steady or temporal) and output volume (low dBA or high 
dBA). 

Depending on the system supporting the device loop, the base 
can: 

• 

Follow the state of the device it supports 

• 

Be controlled and configured for other operating modes 
through front panel programming or the configuration utility 

The base uses the same address and programming label as 
the detector it supports. 

Installation 

Cautions

 

• 

To avoid accidental damage to the control panel, 
disconnect all power before wiring the unit. 

• 

Electrical supervision requires the wire run to be broken at 
each terminal. Do not loop the signaling circuit field wires 
around the terminals. 

Note: 

Always connect the base to a continuous voltage, 

whether the output tone is set to steady or temporal. 

Sleeping rooms: 

In sleeping areas, use the high dBA output 

and temporal tone settings. However, if the control panel is 
producing the three-tone temporal evacuation signal, then the 
high dBA output and steady tone settings are permissible. 

AB4G-SB: 

When using the AB4G-SB box, install a reinforcing 

plate at every knockout. (Reinforcing plates are included with 
the box.) Remove the knockout first and then slide the 
reinforcing plate into the plastic housing. After the plate is in 
place, install the conduit connector and nut. See Figure 1.  

Typically, the base is configured to produce a high dBA 
temporal tone and is connected to a notification appliance 
circuit that outputs a continuous 24 VDC signal. If the 
notification appliance circuit outputs a temporal signal, 
configure the tone setting on the base for steady. 

To install the base: 

1.  The unit default is for high dBA output. To set the output to 

low dBA, cut the circuit board trace as marked on the back 
of the PC board. See Figure 3. 

2.  The unit default is for temporal pattern output. To set the 

output to steady tone, cut the circuit board trace as 
marked on the back of the PC board. See Figure 3. 

3.  Select and install a compatible electrical box, and bring 

the field wiring into the box. 

4.  Install the trim ring and secure using screws. The trim ring 

is included with the SB4U base. See Figure 2. 

5.  Make all wiring connections as shown in Figure 3. 

6.  Attach the base plate to the electrical box using the 

screws provided with the electrical box. 

7.  Attach the trim ring to the base plate. Align the marks on 

the trim ring and base plate, press the trim ring onto the 
base plate, and then rotate the trim ring until it locks into 
place. 

8.  Attach the desired detector to the base. Align the arrows 

on the detector and trim ring, press the detector into the 
base, and then rotate the detector until it locks into place. 

9.  Apply power and activate the unit to verify that it is 

operating properly. 