Prod uct  Han d b ook  

 

 

A D84C01KNX 

A n al og / Digit al Mod u l e 8 In p u t  / 4 l ed  Out p u t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Docum en t  

 

Version

1.1 

Dat e: 

 

 

31/01/2019 

 

Summary of Contents for AD84C01KNX

Page 1: ...6 I 20025 Legnano MI Italia Tel 39 0331 500802 Fax 39 0331 564826 E m ail info eelectron com Web w w w eelectron com C F e P IVA 11666760159 Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 1 27 Product Handbook AD84C01KNX Analog Digit al Module 8 Input 4 led Out put Docum ent Version 1 1 Date 31 01 2019 ...

Page 2: ...Input counter pulse counter 10 Set RGB color 10 MUR DND 10 Loop am ong values 10 7 Led output 11 8 Analog inputs 11 Tem perature sensor description 11 Tem perature sensor param eters 12 9 Therm ostat Function 12 Setpoint Settings 12 SETPOINT Object 12 HVAC MODE obj sw itched heat cool 12 HVAC MODE obj autom atic heat cool 13 SETPOINT COMFORT STANDBY ECONOMY 13 COMFORT Object 13 WINDOW CONTACT Obje...

Page 3: ...666760159 Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 3 27 10 Therm ostat behaviour on bus failure recovery and dow nload 20 Behaviour on bus voltage failure 20 Behaviour on bus voltage recovery 20 Behaviour on ETS Dow nload 20 11 Logics 20 12 Virtual holder 22 How it w orks 22 Com m unication Objects 23 Param eters General 23 Param eters Rem ote inputs 24 Rem ote Sensor Inputs Global E...

Page 4: ...be com pletely excluded We therefore cannot accept any liability for this Any necessary corrections w ill be incorporated into new er versions of this m anual Sym bol for relevant inform ation Sym bol for w arning DISPOSAL The crossed out bin sym bol on the equipm ent or packaging m eans the product m ust not be included w ith other general w aste at the end of its w orking life The user m ust tak...

Page 5: ... 3 com m ands that m ix 1 bit 1 byte objects w ith different group addresses in short and long press m ode or in sw itching m ode x Dim m er m anagem ent w ith single button or w ith double button x Roller shutters and blinds m anagem ent w ith single button or w ith double button x Control sequences w ith 1 bit to m anage sw itching on off lights or row s of lights x Input counters only inputs fr...

Page 6: ...be considered x KNX bus allow s you to rem otely send com m ands to the system actuators Alw ays m ake sure that the execution of rem ote com m ands do not lead to hazardous situations and that the user alw ays has a w arning about w hich com m ands can be activated rem otely For further inform ation please visit w w w eelectron com 4 Param et ri Generali KNX PARAMETER SETTINGS Delay on Pow er up ...

Page 7: ...Configurat ions for 1 bit object On Off Toggle Configurat ions for 1 byt e object Value 0 255 generic signed int Value 0 100 scaling value in steps of 5 HVAC Mode DPT_HVACMode 20 102 KNX PARAMETER SETTINGS Cyclic sending w hen but t on pressed Never 0 3 sec 0 4 sec 0 5 sec 0 8 sec 1 0 sec 1 2 sec 1 5 sec 2 0 sec 3 0 sec 5 0 sec 8 0 sec 10 sec As long as the button is pressed the telegram w ith sel...

Page 8: ... long press operation Param eter Minim u darker behaviour and step of each long press action Shut t er and Blinds le to control Roller Shutters or Blinds using short and long press of the buttons Each input uses 2 com m unication objects 1 bit dim ension for STEP STOP com m and associated to short press operation 1 bit dim ension for UP DOWN com m and associated to long press operation associated ...

Page 9: ...m ands to each elem ent of the sequence or decide to send com m ands only on one of the tw o events The w aiting tim e betw een a com m and and the next is fixed in 1 second Each object com m unication can be connected to a different group address For exam ple it is possible to define a sequence ob j d im en sion sh ort p ress op erat ion 1 lon g p ress op erat ion 2 A 1 bit ON to actuators OFF to...

Page 10: ...ach other as a single im pulse this is necessary w hen the contact connected to the input has a debounce for a certain tim e Set RGB color This function allow s you to associate a short press of the button to a com m and on the bus in order to set a RGB color The RGB object type param eter defines w hether the com m and is sent w ith a single 3 byte object or 3x1 byte objects It is also possible t...

Page 11: ... is OFF Alw ays ON Led is ON Bus controlled Led is lit on or off upon the telegram receive from bus initial state and led behaviour fixed or blink can be configured 8 Analog input s For inputs 5 6 7 and 8 if configured as analog inputs for tem perature probe the NTC probes code eelectron m ust be used TS01A01ACC da 20 C a 100 C TS01B01ACC da 50 C a 60 C tw isted cable At each input it is possible ...

Page 12: ...C TS01A01ACC 50 C 60 C TS01B01ACC Low er set point value 20 C 100 C TS01A01ACC 50 C 60 C TS01B01ACC Telegram w hen value is above set point off on nothing Telegram w hen value is below set point off on nothing Cyclic sending t im e of t elegram s No cyclic send 30 m in 1 hour 2 hours 9 Therm ost at Funct ion The tem perature function can be configured as a therm ostat to control the tem perature o...

Page 13: ... pow er dow n Use these com m unication objects to change current setpoint for every HVAC Mode according to the current active control heating or cooling KNX PARAMETER SETTINGS Act ion t o execut e for set point m odify relative m odify absolute If you set this param eter to m odify relative the therm ostat w ill take into account the new value set but w ill still consider the setpoint set in ETS ...

Page 14: ...also w hen the setpoint value received on this object changes KNX probe t em perature obj It is possible to enable the reading of a second external probe w hich sends the m easurem ent data to the therm ostat via the com m unication object ADDITIONAL TEMPERATURE of size 2 bytes Surveillance t im e for KNX probe 10 255 m in Whenever the therm ostat receive a valid data from KNX probe it consider th...

Page 15: ...ure using the proportional algorithm outside It drives actuator alw ays in ON or OFF When tem perature is inside this range device w ait the end of the cycle tim e before calculating the duty cycle of the next cycle When tem perature is outside of this range below cooling m ode it starts a new cycle as soon as tem perature enters the Bp Int egrat ion t im e Ti 5 250 m in Defines the integration ti...

Page 16: ...on differential in cooling for V1 V2 TdrV2V3 regulation differential in cooling for V2 V3 VALVE ON VALVE OFF V2 ACTIVE V1 ACTIVE V1 ACTIVE VENTILATION OFF V3 ACTIVE REGULATION DIFFERENTIAL V1 SP TEMP SP Tsp REGULATION DIFFERENTIAL V1 V2 REGULATION DIFFERENTIAL V2 V3 TEMP SP TdrV1V2 TdrV2V3 TEMP SP TdrV1SP TEMP SP TdrV1V2 VALVE ON VALVE OFF V2 ACTIVE V3 ACTIVE V1 ACTIVE VENTILATION OFF V1 ACTIVE TE...

Page 17: ... control PI Logic and param eters are the sam e used in On off w ith PWM control m ode the difference is that now the proportional value is sent to the bus via a 1 byte object form at as a value from 0 to 100 This m ode is useful to control fan coils selecting 2 or 4 pipes or generic proportional actuators as valve drivers only linking the 1 byte com m unication object and avoiding to link the val...

Page 18: ...C For the additional valve in 6 w ay m ode it is possible to define different control differentials around the setpoint value as show n below This m akes it possible to adjust the opening and closing of the additional valve independently of the speed control for exam ple once the setpoint has been exceeded a m aintenance action can be taken keeping the valve open again w ithout activating the spee...

Page 19: ... or in short circuit the control action is interrupted and the controlled actuators are sw itched off The value of tem perature sent on the bus in case of probe disconnection or short circuit or for out of range m easured value is 0 C according to KNX DPT_Value_Tem p 9 001 Tem perat ure alarm object Alarm objects are available for each therm ostat and for each tem perature probe in case of probe f...

Page 20: ... are recom m ended to set the behaviour of actuator in order to sw itch the heating cooling equipm ent off after bus pow er on Behaviour on ETS Dow nload s possible to set initial value of Heat Cool m ode HVAC Mode Ventilation For other com m unications objects the behaviour is identical to bus voltage recovery 11 Logics The logic functions are organized into groups of 3 objects 2 inputs and 1 out...

Page 21: ...ss or equal t o 2BYTE_F is received then a telegram 0 1 or nothing is sent When a value great er than 2BYTE_F is received then a telegram 0 1 or nothing is sent IN1 is a 2 bytes float IN2 is disabled OUT is a bit 4 byte float threshold 1 ETS param eter 4BYTE_F When a value less or equal t o 4BYTE_F is received then a telegram 0 1 or nothing is sent When a value great er than 4BYTE_F is received th...

Page 22: ...o Km h x Quotation m arks m ust not be included in expressions x If w rong or unrecognized characters are used in expression then it w ill be not processed and discarded 12 Virt ual holder Virtual holder is activated by enabling corresponded The application field is typically the hotel room w here by using this feature you can rem ove the Holder for access control This logical m odule provides a s...

Page 23: ...om is guest service or m aintenance VH Addit ional Out put OUT 1 byt e This CO is used to send com m ands in event of presence and absence Com m ands can be set different if the room in booked or not and if the person w ho enter the room is guest service or m aintenance Param et ers General KNX PARAMETER SETTINGS Presence w ait t im e 1 m in to 3 hours the opening and consequent closing of the doo...

Page 24: ... the com m unication object VH Rem ote Input x Presence is linked to a presence detector KNX com m unication object Bus sniffer set this option if the com m unication object VH Rem ote Input x Sniffer is linked to a generic CO used in the room Usage of t he Bus Sniffer Opt ion When a person occupies a room interacts w ith it Turning on or off a light in the m ain room or in the bathroom gives indi...

Page 25: ...ed and configured The principle is to connect the sensors door presence and sniffer of room 1 to room 2 and vice versa how ever the Subordinate to Rem ote Inputs Enable param eter for each single Rem ote Input should be properly configured For sensors located in Room 1 this param eter m ust be set to not subordinate on room 1 Virtual Virtual Holder The sam e principle m ust be applied to room 2 se...

Page 26: ...on SpA Via Monteverdi 6 I 20025 Legnano MI Italia Tel 39 0331 500802 Fax 39 0331 564826 E m ail info eelectron com Web w w w eelectron com C F e P IVA 11666760159 Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 26 27 DIA GRA M OF LOGICA L CONNECTIONS FOR VIRTUA L HOLDER LOGIC MODULE ...

Page 27: ...ia Monteverdi 6 I 20025 Legnano MI Italia Tel 39 0331 500802 Fax 39 0331 564826 E m ail info eelectron com Web w w w eelectron com C F e P IVA 11666760159 Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 27 27 DIAGRAM OF LOGICAL CONNECTIONS FOR REMOTE SENSOR INPUT ENABLE GLOBAL ENABLE FIG 2 ...