Eelectron Spa
IN00B02WEBFI00070102_ADMIN_MANUAL_EN.DOCX
7/113
HARDWARE INSTALLATION
INSTALLATION
HORIZONE SERVER
is designed for installation on a 35 mm DIN rail. It requires a 12/24 VDC
power
supply, not included.
For a correct functionality, the following connections must be guaranteed:
Power supply 12V/24V DC (current consumption 240 mA at 12VDC) using the supplied connector.
KNX bus connection via supplied connector.
Network connection via CAT.5 network cable (not supplied).
The LED marked with the label "POWER" on the front of the server signals that the device is ON
The LED labeled
“SERVICE” remains off under normal circumstances.
Furthermore,
HORIZONE SERVER
has the following interfaces:
SD-slot: in the future will be used to expand the memory of
HORIZONE SERVER
through any
compatible SD Card. Please note that this peripheral at the moment is not actually used.
RS232-interface and 2 USB-ports: for integration of third party systems.
the connection to the KNX bus is not really needed for the configuration of
HORIZONE
SERVER
, but it allows a more efficient programming, since direct tests of the system
can
be performed.
When commissioning
HORIZONE SERVER
, the following steps must be followed:
Power off the system.
Install
HORIZONE SERVER
on the DIN-Rail.
Connect power supply and KNX bus to
HORIZONE SERVER
Power on the system.
Wait until complete boot up of
HORIZONE SERVER
.
To ensure appropriate protection to the
HORIZONE SERVER
hardware and prevent
damages, please consider installing appropriate lightning and surge protection devices
on power supply. To grant full operation under any situation, please consider also
installing an Uninterruptible Power Supply (UPS).
If the
HORIZONE SERVER
hardware is altered in any way, irreversible damage can
occur. Any intervention on the equipment should be performed only by skilled personnel
authorized by
EELECTRON SPA
.