Unblocking a DALI device or group
The device is in continuous manual mode.
o
Press
c
button briefly as many times as necessary until the display (4) flashes the desired
DALI number.
o
Press
ON/
n
and
OFF/
o
buttons simultaneously for at least 5 seconds.
DALI device or group is enabled.
The display (4) no longer flashes.
o
Activate bus mode (see section Deactivating permanent manual control).
5 Information for electrically skilled persons
5.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.
Fitting the device
Observe the temperature range. Ensure adequate cooling.
o
Mount device on DIN rail. Output terminals must be at the top.
Connecting the device
Figure 3
Control cable: appropriate type, cross-section and routing for the specifications for 250 V
cables. DALI and mains voltage wires can be run together in a cable, e.g. NYM 5x1.5 mm².
i
DALI participants from some manufacturers have expanded functions and can e.g. be
controlled via mains voltage on the DALI connection. When existing DALI installations are
refitted, remove all corresponding operator controls.
i
The DALI control voltage is a functional extra-low voltage (FELV). When performing
installation, perform the installation in such a way that when an area is disconnected the
lines carrying both the DALI and also the mains voltage are disconnected.
o
Connect device as shown in the connection example (Figure 3).
5/9
IC00P01DAL -
DALI gateway