IO22C02KNXFI01010001.doc

 

 

                                

 

 

Inwall 2 Input / Output Module

 

 
IO22C02KNX 
      

Product and Applications description 

 

The  product  is  dedicated  to  interfacing  free potential contacts 
through  the  2  input  channels,  for  example sensors, traditional 
buttons,  etc.  and  2  output  channels  at  low  voltage  for  drive 
signal  lamp  or  LED  for  example  for  synoptic  panels  used  for 
monitoring the installation.  
 
The  device  is equipped with appropriate communication inter-
face with the bus type TP1 (twisted pair) KNX European stan-
dard, according CEI EN 50090. 

 

Application Program

Application Program

Application Program

Application Program    

 
Downloadable from website: 

www.eelectron.com

 

 
Maximum number of group addresses: 

30

30

30

30

 

This is the maximum  number of different group addresses the 
device is able to memorize. 
 
Maximum number of associations: 

30

30

30

30

 

This  is  the  maximum    number  of  associations  between  com-
munication  objects  and  group  addresses the device is able to 
memorize. 
 

Caution

Caution

Caution

Caution

:  each  transmission  object  has  usually  associated  a 

single  group  address. If  you  want  to  associate  to  a  transmis-
sion  communication  object  other  addresses  in  addition  to  the 
first, please note that you can add a maximum of 16 group ad-
dresses of this kind for the whole device. 
 

Technical data

Technical data

Technical data

Technical data    

 

Power Supply: 

 

 

 

Via bus EIB/KNX cable 

  Voltage     

 

21..30V DC 

  Current Consumption EIB/KNX 

< 10mA 

 

Input

Input

Input

Input    

 

  Number: 2 free contacts 

  Maximum  Length of Connecting Cable:          

 10m 

  Voltage Scanning: Vn – 3,3 V DC (internally Generated) 

 

Output

Output

Output

Output        

 

  Number:  2 outputs for drive led – Max 0,5 mA 

    
Control 

Control 

Control 

Control Elements

Elements

Elements

Elements    

 

  Red LED and button EIB/KNX for programming the physical 

address 

 

Connections 

 

  EIB/KNX  2 Terminals for connections bus with 0,8mmØ 

 

  Input 

2  connector cable to be wired with 24 AWG 

 

  Output 

2 connector cable to be wired with 24 AWG 

 
 
 
 

Electrical 

Electrical 

Electrical 

Electrical Pattern

Pattern

Pattern

Pattern    

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

Mechanical Data

Mechanical Data

Mechanical Data

Mechanical Data    

• Case: plastic  
• Protection class: II in accordance with EN 61140  
• Dimensions: (width x height. X depth.): 43 x 36 x 17 mm  
• Weight: approx. 30 g 
 
 
 

 

 

    

Electrical Safety  

 
• Degree of pollution (IEC 60664-1): 2  
• Degree of protection (EN 60529): IP 20  
• Protection class (according to IEC 1140): III  
• Overvoltage class (according to IEC 664-1): III  
• Bus: safety voltage SELV DC 24 V  
• Meets EN 50090 and IEC 664-1: 1992 

 
EMC Requirements  

 
Complied with EN 50081-1, EN 50082-2 and EN 50090-2.2 

 

Terms of use  

 
• According to EN 50090-2.2  
• Ambient temperature during operation: 0 °C + 45 °C  
• Storage temperature: - 20 °C + 55 °C   
• Relative humidity: max 90% 

    
Certification

Certification

Certification

Certification    

 
EIB/KNX certificate 

 

CE Mark 

 
According to EMC guideline and low voltage directive 

 
 
 

Indicators Position and Control Elements

Indicators Position and Control Elements

Indicators Position and Control Elements

Indicators Position and Control Elements    

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Wired Connectors: 

 

1. 

BLACK COMMON INPUT 1 

2. 

WHITE INPUT 1 

3. 

YELLOW OUTPUT 1 

4. 

BLACK COMMON OUTPUT 2 

5. 

n.c 

6. 

n.c 

7. 

BLACK COMMON INPUT 2 

8. 

GREEN INPUT 2 

9. 

BLUE OUTPUT 2 

10.  BLACK COMMON OUTPUT 2 
11.  n.c. 
12.  n.c. 
15.  Terminal Connection Bus (graft): 

-  negative pole Black 
+  positive pole Red 

 
Control Unit And Display: 

 

14.  ETS programming led 
13.  ETS programming switch 
 
 
 
 
 

 

 

Installation Instructions 

 
The device may be used for permanent indoor installations 
in dry locations within wall box mounts. 
 

WARNING 

  The device must not be connected to 230V cables 

  The prevailing safety rules must be heeded. 

  The device must be mounted and commissioned by an 

authorised installer. 

  The applicable safety and accident prevention regula-

tions must be observed. 

  The device must not be opened. Any faulty devices 

should be returned to manufacturer. 

  For planning and construction of electric installations, the 

relevant guidelines, regulations and standards of the re-
spective country are to be considered. 

 
 

Mounting and Wiring hints 

 
General Description 

The  device  configuration  (KNX  physical  address  assign-
ment) is done by pressing the programming push button  lo-
cated in the back side of the housing. Please take care dur-
ing installation to leave connection wires long enough in or-
der  to  remove  the  device  easily  from  the  wall  box  for  com-
missioning. 

 
Connecting bus cables

 

  Connect  each  single  KNX/EIB  bus  core  inside  the  termi-

nal block observing bus polarity . 

  Slip  the  bus  connection  block  into  the  guide  slot  placed 

on the back side of this device and press the block down 
to the stop. 

 
 
 
For further information please visit 

www.eelectron.com

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

eelectron spa 

Via Magenta 77/22  
I-20017 Rho (MI) - Italia  
Email: info@eelectron.com 
Web: www.eelectron.com

 

 
 

KNX 

INTERFACE 

 

 

 

 

 

 

 

10 

COM1 

 

IN1 

 

OUT1 

 

COM2 

 

COM3 

 

IN2 

 

OUT2 

 

COM4 

BLACK
WHITE
YELLOW
BLACK

GREEN
BLUE

BLACK

BLACK









10 
11 
12 

13 

14 

15 

Reviews: