object (“Valve 0=Cold / 1 = Warm”) in order to open or close the valve
connected to an actuator.
Option “4
Tubes Circuit ON/OFF”:
with this option the HVAC plan is composed
of 4 circuits with ON/OFF switching Cold and Warm valves. The thermostat
provides two 1 bit object, one dedicated to control the Warm valve and the other
to Cold valve via an external bus actuator.
Option “2
Tubes Circuit Proportional”:
with this option the HVAC plan is
composed of 2 circuits with proportional Cold and Warm valves. The thermostat
provides here one 1 byte object (“Valve Proportional 0%=Cold / 100%=Warm”)
with only two values: 0% (cold) and 100% (warm).
Option “4
Tubes Circuit Proportional”:
with this option the HVAC plan is
composed of 4 circuits with proportional Cold and Warm valves. The thermostat
provides here two 1 byte object (“Warm Valve Proportional” and “Cold Valve
Proportional”) with only two values: 0% (valve completely closed) and 100%
(valve completely opened).
Fancoil Type
Options:
Single Speed V1
Double Speed V1-V2
Three Speed V1-V2-V3
Proportional Regulation
Option “
Single Speed V1”:
the fan coil has only 1 speed and is so controlled with
a 1 bit object (“Fancoil Speed V1”) via an external bus actuator.
Option “
Double Speed V1-V2”:
the fan coil has two speeds V1 and V2. With this
option the device provides two 1 bit objects to control the two speeds (“Fancoil
Speed V1” and “Fancoil Speed V2”) via an external bus actuator.
Option “
Three Speeds V1-V2-V3
the fan coil has three speeds V1,V2, V3. With
this option the device provides three 1 bit objects to control the three speeds
(“Fancoil Speed V1”, “Fancoil Speed V2”, “Fancoil Speed V3”) via an external
bus actuator.
Option “
Proportional Regulation”:
the fan coil is controlled by proportional
actuator that allows fan coil speed proportional control between da 0 a 100%.
Temperature Sensor Adjust
Options:
-1,5°C….0,0…..+1,5°C
This parameter can be useful when a temperature adjustment is required by the
internal sensor (e.g. due to wrong or difficult installation). The adjustment should
be set using an external professional temperature sensor in order to check the
temperature variance that occurred.