Pagina
18 di 30
Setpoint Antifreeze Winter
Options:
+
4°C….+7°C…..+10°C
Setpoint for frost protection (in Winter/Heating mode).
The frost protection is activated via bus with the 1 bit object “Antifreeze” or in
case the function “Window Switch” is associated to the binary input available. If
a window is opened and this status is detected through the binary input channel
interfaced with a window contact so the HVAC system is switched OFF
immediately.
In “Antifreeze” mode the thermostat refers to this setpoint switching OFF the
HVAC plant in order to avoid energy and heating waste.
The Heat protection for cooling function is not handled in this product version.
Guest Permit Regulation (+/- °C)
Options:
No Variation,
±1°C….±3…..±5°C
With this parameter the setpont range of variation allowed to the user, using the
front push buttons, can be limited to a maximum of
±5°C.
Note: the user setpoint variation is stored and maintained inside in case of
change from Comfort to Standby mode and vice versa. In case the thermostat
pass from Comfort mode to Economy or Antifreeze mode or the setpoint is
changed via bus with the specific object than the user modification is cancelled
(i.e. the Comfort setpont is restored to value before user modification).