If the input is associated to “Windows Switch” function the following parameters are
visible and enabled.
Windows Switch Mode
This parameter allows the input contact usage setting if normally opened or
closed.
Options:
Normally Open
Normally Close
Option “
Normally Open”
:
Window Close = contact open
Window Open = contact closed.
. Option “
Normally Close”
:
Window Close = contact close
Window Open = contact open.
Cyclic Send
Options:
ON
OFF
This parameter enable the cyclical sending of current value of the binary Input
to the bus at a set interval.
Cycling send time (min)
Options:
1…10…200
The cyclic time for sending telegrams repeatedly on the bus with Input current
value is specified here. The time units are minutes.
Note:
please see Input timing diagrams in “Application Notes”.
In case the binary input function selected is “General Purpose” so the following
parameter appears to allow planner to set the input signal handle based on
rising/falling edges or toggle ON/OFF.