Pagina
25 di 30
5 Communication Objects
The EIB/KNX communication objects provided within the application program
“
EEL_RTH1_10 Room Thermostat
” are the following:
Fig. 11:Communication Objects EIB/KNX provided with the application program
(NB: some objects are visible only if enabled by specific parameter setting).).
Nr.
Funzione
Nome
Tipo
Flag
0
On/Off
0=Standby / 1=Comfort
EIS1, 1bit
DPT 1.001
C,R,W,T
After receiving the object from the bus, the thermostat goes to standby mode (when
receiving 0) or in Comfort mode (when receiving 1).
The fixed temperature Set point is used when passing from Comfort mode to Standby
mode and vice versa. When changing mode, a thermostat that was working in manual
gets to automatic mode.
1
On/Off
Economy
EIS1, 1bit
DPT 1.001
C,R,W,T
After receiving the object from the bus, the thermostat goes in Economy mode (e.g.
“Night mode”).
The fixed temperature Set point is used when passing to this mode. When changing
mode, a thermostat that was working in manual gets to automatic mode.
2
On/Off
AntiFreeze
EIS1, 1bit
DPT 1.001
C,R,W,T
After receiving the object from the bus, the thermostat goes in Antifreeze mode.
The fixed temperature Set point is used when passing to this mode. When changing
mode, a thermostat that was working in manual gets to automatic mode.
In case the input has been enabled with the function “Windows Switch” as the
antifreeze object is received the thermostat switches OFF the heating/cooling system.