Pagina
26 di 30
Nr.
Funzione
Nome
Tipo
Flag
3
On/Off
0 = Summer / 1=Winter
EIS1, 1 bit
DPT 1.001
C,R,W,T
After receiving the object from the bus, the thermostat goes in Winter mode (when
receiving 1) or in Summer mode (when receiving 0).
The fixed temperature Set point is used when passing from Winter mode to Summer
mode and vice versa.
Note: the thermostat TM11A01KNX (TM11A11KNX) doesn’t toggle automatically
between Summer (Cooling) and Winter (Heating) mode but only by receiving this object
from the bus.
4
Real actual setpoint
Actual SetPoint
EIS5, 2 byte
DPT 9.001
C,R,W,T
With this object the real last setpoint value, concerning the actual operating mode
(summer/winter and comfort, economy or standby) is sent to the bus.
The real actual value is calculated from the base setpoint ± the user variation
introduced with the front push buttons.
This object is sent cyclically (if enabled with specific parameter) or at any changes or
after ETS download.
5
Comfort setpoint value
setting
Setpoint Base Comfort
EIS5, 2 byte
DPT 9.001
C,R,W,T
This object is used to set the Comfort base setpoint via bus, normally by a centralized
unit. This value is stored in a non volatile memory.
6
Standby setpoint value
setting
Setpoint Base StandBy
EIS5, 2 byte
DPT 9.001
C,R,W,T
This object is used to set the Standby base setpoint via bus, normally by a centralized
unit. This value is stored in a non volatile memory.
7
Economy setpoint
value setting
Setpoint Base Economy
EIS5, 2 byte
DPT 9.001
C,R,W,T
This object is used to set the Economy base setpoint via bus, normally by a centralized
unit. This value is stored in a non volatile memory.
8
Actual temperature
value
Actual Temperature
EIS5, 2 byte
DPT 9.001
C,R,W,T
Acutal temperature is transmitted to the bus with this object. The temperature value is
sent in case of temperature variation or, if enabled by the parameter, cyclically.