Pagina
27 di 30
Nr.
Funzione
Nome
Tipo
Flag
9
Binary Output object
Relay OnBoard
EIS1, 1bit
DPT 1.001
C,R,W,T
If the output is configured with “General Purpose” function this object is visible and is
used to control the output relay from the bus (e.g. from an external KNX sensor or push
button) as a normal binary output channel.
If the function “Velocity V1 Fancoil” is assigned this object is not enabled (i.e. the relay
is used only to control the speed V1 of a fan and so not free for different usage).
10
Binary Input
Windows Switch
Digital Input
EIS1, 1bit
DPT 1.001
C,R,W,T
In case of window sensor configuration, the device controls the automatic fancoil stop
when the window is opened (internally changes into antifreeze mode) and sends the
value to the bus.
In case the input is configured for general purpose usage the “Digital Input” object is
visible and transmits an ON/OFF signal regarding the input state to an external actuator
(and/or to a visualization software).
11
Speed V1 command to
fan coil
Fancoil Speed V1
EIS1, 1bit
DPT 1.001
C,R,W,T
It transmits on the bus the V1 speed command directed to an external actuator.
12
Speed V2 command to
fan coil
Fancoil Speed V2
EIS1, 1bit
DPT 1.001
C,R,W,T
It transmits on the bus the V2 speed command directed to an external actuator.
13
Speed V3 command to
fan coil
Fancoil Speed V3
EIS1, 1bit
DPT 1.001
C,R,W,T
It transmits on the bus the V3 speed command directed to an external actuator.
14
Fan coil proportional
speed regulation
Fancoil Speed Proportional
EIS6, 1 byte
DPT 5.001
C,R,W,T
In case with the parameter “Fancoil Type” the “Proportional Regulation” is selected this
1 byte object is used to send fan coil speed values between 0% and 100% to
proportional fan coil actuator.