UPS: OFFICE 400 - 2000
Storage and Unpacking
OFFICE Series
24
4.
Storage and Unpacking
4.1
Storage of the UPS
If the UPS is to be put in storage after delivery, it is imperative to observe the
following instructions:
–
Always leave the device and accessories in the original packaging;
–
Never store the UPS upside-down;
–
The recommended storage temperature should be between 10
–
25°C. The maximum temperature values may never be exceeded
(see also
13 Technical data);
–
The delivered goods must also be protected against moisture. The
device must therefore be stored in a dry area;
–
If the storage period exceeds four months, the UPS must be con-
nected with the mains power supply for approximately 24 hours to
avoid a total discharge of the accumulators, which would result in ir-
reversible damage to the accumulators.
4.2
Transport to the installation site
As the point of delivery is usually not the point of installation, the equipment has
to be transported to the installation site. Please follow these instructions for the
transport of the UPS:
–
Always transport the delivery in the original packaging as close as
possible to the installation site;
–
Always transport the UPS in the specified transport position. Do not
transport the device upside-down;
–
Also mind the specified center of gravity when transporting the de-
vice;
–
There is always a general risk of tipping or tilting with devices where
the center of gravity is located in a high position;