background image

KDL1-series

Caution!

Only personnel qualified to work with high voltage circuits are allowed to do the installation. 

Make  sure  that  the  circuits  are  disconnected  from  the  voltage  supply  and  correctly 

grounded. Never work on live circuits. Voltage of primary circuit is lethal. Make sure that 

the outer diameter of cable and the diameter of cable insulation are compatible.

EFLA Type Conductor Size

(mm

2

)

AWG Cable Diameter

(mm/inch)

Diameter at Wire 

Insulation 

(mm/inch)

Diameter, Length 

of Assembly 

(mm/inch)

KDL1

6

8**

9.0 – 17.0 mm

0.354 – 0.669”

7.5 – 13.0 mm

0.295 – 0.512”

42 mm, 276 mm

1.654”, 10.886”

KDL1.6 

10*

6

9.0 – 17.0 mm

0.354 – 0.669”

7.5 – 13.0 mm

0.295 – 0.512”

42 mm, 276 mm

1.654”, 10.866”

* 16mm² stranded, ** up to 19 strands 
Follow  the  local  instructions  for  safety  precautions  or  refer  to  the  FAA  advisory  circular  AC 

150/5340-26 Maintenance of Airport Visual Aid Facilities. In addition, follow Advisory circular 

AC 150/5370-10 Part-XI Lighting Installations. Always test the installation according to above 

mentioned documents and local regulations.

Make sure that dimensions of the cable comply with the type of connector used. In case 

any kind of non-compliance, do not proceed with the installation. If any damage has 

occured to the connectors or cables, do not proceed with the installation. 

For more information about the products, please visit us at 

www.efla.net

PRIMARY CONNECTOR KIT 

Summary of Contents for KDL1 Series

Page 1: ...6 KDL1 6 10 6 9 0 17 0 mm 0 354 0 669 7 5 13 0 mm 0 295 0 512 42 mm 276 mm 1 654 10 866 16mm stranded up to 19 strands Follow the local instructions for safety precautions or refer to the FAA advisory circular AC 150 5340 26 Maintenance of Airport Visual Aid Facilities In addition follow Advisory circular AC 150 5370 10 Part XI Lighting Installations Always test the installation according to above...

Page 2: ... towel G A B H C E F D Contents Use proper tool when installing Efla products The recommended crimping tools are following Elpress GWB 4099C KLAUKE K05 6 KLAUKE K18 Efla is able to assist you in installation problems and questions about correct installation The recommended crimping tools are available in Efla For more information please visit www efla net ...

Page 3: ...mp at two positions Turn the cable min 90o between the two crimps Size 6 for KDL1 Size 8 for KDL1 6 90 Crimp Crimp Assembling the receptacle connector 4 Press the guiding tool E into the receptacle socket C 5 Place the measuring tool F into the receptacle housing A 6 Push the cable with the socket E through the receptacle housing A Use the measuring tool F to avoid pushing too far 7 Tighten the ca...

Page 4: ...ports around the world EFLA OY Kipinätie 3 FI 06150 Porvoo Finland tel 358 0 20 198 0190 www efla net Assembling the Plug Connectors 9 Place the measuring tool F onto the plug housing B 10 Push the cable with the pin D through the plug housing B Use the measuring tool F to avoid pushing too far 11 Tighten the cable gland until the connector is properly sealed Max torque 8 Nm 5 9 lb ft torque 12 Re...