- 2 -
eFlow104N Series Installation Guide
Overview:
Altronix eFlow104N power supply/chargers convert a 120VAC / 60Hz input to a 24VDC nominal output
(see Power Supply Configuration Reference Chart and Specifications)
.
eFlow104N Series Power Supply Configuration Reference Chart:
Altronix Model Number
Nominal DC
Outputs
Maximum Supply Current for Main and Aux. Outputs (A)
Input Rating: 120VAC, 60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution Modiule
Number of Outputs
Fused Outputs Ratings
PTC Protected Class 2 Power-Limited Auto-Resettable Outputs Ratings
Accommodates up to 7AH Batteries
Accommodates up to 12AH Batteries
[DC]
[AUX]
24VDC Output Range (V)
24VDC Output Range (V)
eFlow104N
20.17-
26.4
20.28-
26.4
10A
4.5A 6.3A/
250V
15A/
32V 700
N/A
1
–
–
P
–
eFlow104NX
–
–
–
P
eFlow104N8
20.17-
26.4
20.28-
26.4
10A
4.5A 6.3A/
250V
15A/
32V 700
PD8UL
8
2.5A
–
P
–
eFlow104NX8
2.5A
–
–
P
eFlow104N8D
20.0-
26.4
20.28-
26.4
10A
4.5A 6.3A/
250V
15A/
32V 700
PD8ULCB
8
–
2A
P
–
eFlow104NX8D
–
2A
–
P
eFlow104N16
20.17-
26.4
20.28-
26.4
10A
4.5A 6.3A/
250V
15A/
32V 700
PD16W
16
2.5A
–
P
–
eFlow104NX16
2 - PD8UL
2.5A
–
–
P
eFlow104N16D
20.0-
26.4
20.28-
26.4
10A
4.5A 6.3A/
250V
15A/
32V 700
PD16WCB
16
–
2A
P
–
eFlow104NX16D
2 - PD8ULCB
–
2A
–
P
The following units provide non power-limited outputs: eFlow104N, eFlow104NX, eFlow104N8, eFlow104NX8, eFlow104N16,
and eFlow104NX16.
The following units provide Class 2 power-limited outputs: eFlow104N8D, eFlow104NX8D, eFlow104N16D, and eFlow104NX16D.
If a power-limited output is required in the end-product application, the DC output from the power supply must be connected to a
separately Listed control unit or accessory board that provides power-limited outputs. The product(s) providing the power-limited
output(s) must be listed as appropriate for the particular end-product application (fire alarm, burglar alarm, access control), and
wired in accordance with the products installation instructions. Class 1 wiring methods, separation of circuits, and proper fire-
rated enclosures all must be considered when connecting the DC output of the power supply to the end-product devices. The
auxiliary output of these units are power-limited.
UL Listings for US Installations:
UL 294, 7th edition
- UL Listed for Access Control System Units.
Access Control Performance Levels:
Destructive Attack - I; Endurance - I; Line Security - I;
Stand-by Power: 7AH - I, 12AH - I, 40AH - III, 65AH - IV.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
California State Fire Marshal
European Conformity
Factory Mutual Approved (eFlow104N and eFlow104NX only)
Altronix Corp.
140 58th St. Brooklyn, NY