3.6.1 Emergency Stop
Pull out the short-circuit strip from the terminal block and connect the emergency stop switch into the
series circuit as shown in Fig. 3-2. The recommended wire cross-section should be larger than 0.5 mm².
Fig. 3-2 Wiring of Emergency Stop Switch
Table 3-9 External E-stop Terminal Description
Terminal Sequence
Remarks
1
EMG-AP
2
EMG-AM
3
EMG-BP
4
EMG-BM
5
STOP1-AP
6
STOP1-AM
7
STOP1-BP
8
STOP1-BM
Note: Both terminals 1 and 2 and terminals 3 and 4 are two circuit pairs for external E-stop. Both
terminals 5 and 6 and terminals 7 and 8 are two circuit pairs for the safety door.
The external device needs to detect whether the emergency stop signal of the robot is triggered or not.
Users can pull out the short-circuit strip from the terminal block and insert the external E-stop cables into
the corresponding terminal with a tube pre-insulating terminal end of E0508 type.
E-stop
terminal
on the
E-cabinet
Reserved
E-stop
terminal on
the panel
External E-stop terminal