Pressure sensor
Measurement range
300 – 1100 hPa
Absolute accuracy
±1 hPa
Relative accuracy
±0,12 hPa
Resolution
0,18 Pa
Long-term stability
±1 hPa / Jahr
Hardware and interfaces
Interval between
measurements
1 second
Calibration
Factory-calibrated, DakkS certificate available (German
Accreditation Body)
Sensor heater
Integrated
Ethernet
10/100 Mbit RJ45, HP Auto-MDIX
Static or dynamic IP (DHCP client)
Operating system
Nut/OS 5
Firmware updates
Via web interface, rescue function
Logging interval
Configurable
M2M
HTTP (XML, CSV, JSON), Syslog, Modbus/TCP, SNMP
Data logger capacity
36864 entries ≙ 25 days (1 entry/min) to 4.2 years (1 entry/h)
Web interface
Interactive diagram, live update, HTML5, CSS3, JSON und SVG
Security
StartTLS / TLS, password protection, user management (3 users / 3
groups)
Up to 4 recipients and 2 SMTP servers (StartTLS / TLS)
SNMP
SNMPv1 agent and traps
Status LED
3 colors: red, green, yellow
Time / date
Real-time clock with battery backup and SNTP update
Power supply
5 V DC to 5.5 V DC
Power consumption
120 mA 0.6W (typically), 200 mA 1W (maximally)
Ambient conditions
Operation
-40 °C to 85 °C, max. 95 % rF
-40 °F to 185 °F, max. 95 % rF
Storage
-40 °C to 85 °C, max. 95 % rF
-40 °F to 185 °F, max. 95 % rF
Mechanical data
Casing material
ABS plastic
Casing color
Black RAL 9011
Casing dimensions
2.2 x 1.6 x 0.8 in (56,3 x 40 x 21 mm)
Sensor cable length
13.4 in (340 mm)
Weight
0.07 lb (35 g)
114