9.5 Modbus Registers
Read Registers
Address
Offset
Format
Contents
30011
10
int16
Temperature Celsius * 10
30012
11
int16
Relative humidity %
30013
12
int16
Temperature Fahrenheit * 10
30014
13
int16
Temperature Kelvin * 10
30015
14
int16
Dew point Celsius * 10
30016
15
int16
Dew point Fahrenheit * 10
30017
16
int16
Dew point Kelvin * 10
Holding Registers
Address
Offset
Format
Contents
40021
20
int16
Lower temperature limit Celsius * 10
40022
21
int16
Upper temperature limit Celsius * 10
40023
22
int16
Temperature dead band Kelvin /
Celsius * 10
40024
23
int16
Lower temperature limit Fahrenheit * 10
40025
24
int16
Upper temperature limit Fahrenheit * 10
40026
25
int16
Temperature dead band Fahrenheit * 10
40027
26
int16
Lower temperature limit Kelvin * 10
40028
27
int16
Upper temperature limit Kelvin * 10
40031
30
int16
Lower humidity limit
40032
31
int16
Upper humidity limit
40033
32
int16
Humidity dead band
40051
50
int16
Lower dew point limit Celsius * 10
40052
51
int16
Upper dew point limit Celsius * 10
40053
52
int16
Dew point dead band Celsius * 10
40054
53
int16
Lower dew point limit Fahrenheit * 10
40055
54
int16
Upper dew point limit Fahrenheit * 10
40056
55
int16
Dew point dead band Fahrenheit * 10
40057
56
int16
Lower dew point limit Kelvin * 10
40058
57
int16
Upper dew point limit Kelvin * 10
Appendix
95