7.4 Modbus Registers
Read Registers
Address
Offset
Format
Content
30011
10
int16
Temperature Celsius * 10
30012
11
int16
Relative humidity %
30013
12
int16
Temperature Fahrenheit * 10
30014
13
int16
Temperature Kelvin * 10
30015
14
int16
Dew point Celsius * 10
30016
15
int16
Dew point Fahrenheit * 10
30017
16
int16
Dew point Kelvin * 10
Holding Registers
Address
Offset
Format
Content
40021
20
int16
Lower limit temperature in Celsius * 10
40022
21
int16
Upper limit temperature in Celsius * 10
40023
22
int16
Dead-band temperature in Kelvin /
Celsius * 10
40024
23
int16
Lower limit temperature in Fahrenheit * 10
40025
24
int16
Upper limit temperature in Fahrenheit * 10
40026
25
int16
Dead-band temperature in Fahrenheit * 10
40027
26
int16
Lower limit temperature in Kelvin * 10
40028
27
int16
Upper limit temperature in Kelvin * 10
40031
30
int16
Lower limit humidity in %
40032
31
int16
Upper limit humidity in %
40033
32
int16
Dead-band for humidity
Appendix
46