EGS Electrical Group • 800-621-1506 • www.appletonelec.com

Rev. E 01/15/2009   

Page 1 

300880-1

INSTRUCTION SHEET     

U.S. Patent No. 3,735,078

EBR Receptacles with Interlocked Circuit Breaker:

Explosion-Proof, Dust-lgnition-Proof.

Weatherproof Spring Cover—30, 60, 100 and 150 Amps at 600V A.C. Max.

Interlocked Circuit Breaker Safety Construction. Grounding thru Extra Pole and Shell

*

 CAUTION: To prevent Ignition of hazardous atmospheres, do not use in Class II,

Group F locations that contain electrically conductive dusts. Most coal dusts are not 
electrically conductive.

Class I, Div. 1 and 2
Groups C, D
Class II, Div. 1 and 2
Groups F, G
Class III 
Type 3, 3R, 4

, 4X

NEMA 7CD, 9F*G  

1-1/2” threaded conduit 

openings- one in top and 

two in bottom

I. TO DISASSEMBLE RECEPTACLE INTERIOR

1. Remove polarizing screw and washer.
2. Rotate terminal holder counter-clockwise.

II. TO CONNECT CONDUCTORS TO RECEPTACLE INTERIOR

1. Strip insulation from ends of individual conductors.
2. Loosen screws in pressure connectors and slide prepared ends of conductors into       
    the connectors, observing proper polarity. Tighten screws.

III. TO REASSEMBLE RECEPTACLE INTERIOR

1.Insert Terminal Holder and turn clockwise until front end is approximately 1/4” inside 
    of casting surface. Recessed radial depression in Terminal Holder must be lined up  
    with polarizing washer/locator. Replace screw through the ground strip.

IV. POLARITY AND PHASE ROTATION

1. ACP, CPH Plugs and EBR Receptacle are polarized so that the plug will enter the 
    receptacle only one way. 
2. Special Polarization: suffix - P4 added to catalog number of the receptacle. Prevents 
    plug insertion in a receptacle wired for a different voltage (doesn’t apply for 150 Amp).

Solderless lugs are provided for line connections 
and receptacle is prewired to the load side of 
breaker. Cover-mounted components leave entire 
enclosure space free for pulling of line conductors 
and wiring.

Plug is mechanically locked in receptacle when circuit 
breaker is ON. Design provides interlocked connect and 
disconnect operation as well as short circuit and thermal 
time delay overload protection.  Breaker operating handle 
can be padlocked in either “ON” or “OFF” position and is 
trip-free.

Enclosure has 3/4” threaded openings top and bottom 
for installation of UL Listed drain and breather. Reducers 
are suitable for Class 
I, Groups B, C and D; 
Class II, Groups F and 
G when installed such 
that at least five full 
threads are engaged. 
Unused openings must 
be plugged with fac-
tory supplied plugs.

TERMINAL

HOLDER

POLARIZED SCREW
AND WASHER

PRESSURE

CONNECTORS

SCREW

 Flip cover suitable for Type 3 and 3R only. Select screw cover for 

Type 4 and 4X. Both covers are included with product. Type 4 rating 
maintained with Appleton Type 4 plug installed.