background image

1

RELAY BASES

for Smoke, Heat & Carbon Monoxide Alarms

Instruction Manual

Read and retain carefully for as long as the product is being used.  

It contains vital information on the operation and installation of 

your product. This instruction manual should be regarded as part 

of the product.

If you are just installing this product, this manual must be given 

to the householder. The manual is to be given to any subsequent 

user. 

1. Introduction

The Ei128R & Ei128RBU Relay Bases switch a relay upon receipt 

of an alarm signal from a hardwire interconnection with a mains 

powered Ei Alarm. The electrically isolated relay contacts can be 

used for many applications such as shutting off the mains supply 

to boilers, triggering panels, etc. The Relay Bases are powered by 

230VAC mains - with the Ei128RBU model having recharbeagle 

back-up cells.
The Relay Bases are normally installed directly underneath an 

Easi-fit Alarm base but can also be sited separately.
As supplied the relay operates continuously (e.g. it switches when 

one of the Alarms sounds and switches back when it receives the 

alarm cancel signal). When the slide switch is moved to the pulse 

‘P’ position (see figures 1a & 1b) the relay will switch when the 

Alarm sounds but will automatically switch back after 5 seconds. 

This is commonly used with warden call systems where only 

momentary short circuit signalling is required.

Both the Ei128R and Ei128RBU can be used in 230VAC and low 

voltage applications with the Ei128RBU being best suited for low 

voltage applications.

2. Overview

Models: 

Ei128R

Ei128RBU

LOCATION FOR

SCREWS

Cover

Summary of Contents for Ei128R

Page 1: ...upply to boilers triggering panels etc The Relay Bases are powered by 230VAC mains with the Ei128RBU model having recharbeagle back up cells The Relay Bases are normally installed directly underneath an Easi fit Alarm base but can also be sited separately As supplied the relay operates continuously e g it switches when one of the Alarms sounds and switches back when it receives the alarm cancel si...

Page 2: ...NS TO TERMINAL BLOCK NO NC C VOLT FREE RELAY CONTACT FOR THE CONTROL OF THE AUXILIARY DEVICE C COMMON NC NORMALLY CLOSED NO NORMALLY OPEN DOUBLE INSULATE ALL WIRES VOLT FREE FOR THE C AUXILIARY C COMMO NC NORM NO NORM DOUBLE INS L N IC N IC L PILLARS C CONTINUOUS RELAY CHANGES UNTIL ACTIVATION STOPS Figure 1b Ei128RBU SURFACE CONDUIT CABLE ENTRY P PULSE RELAY CHANGES FOR 5 SECONDS C CONTINUOUS REL...

Page 3: ...ower source that utilises an inverter e g PV solar panel the Total Harmonic Distortion THD must be less than 5 If in doubt please check with the manufacturer of the inverter This also applies to battery powered UPS Uninterruptible Power Supply inverters The Relay Bases must not be powered from a light dimmer circuit WARNING First disconnect the mains from the circuit to be used WARNING To prevent ...

Page 4: ...r to prevent air draughts that could affect the performance of the Alarm to be sited on top 8 Remove the wiring cover on the Alarm mounting plate to view the terminal see fig 3a 9 Connectthethreewires L Live N NeutralandIC Interconnect from the Relay Base to the terminal on the Alarm s mounting plate The IC wire must be connected even if it is a single Alarm installation 9 Replace the wiring cover...

Page 5: ...rminal block Screw tightening torque max 0 5Nm 5 1kgf cm 4 Screw the Relay Base in place 5 3 Wiring the relay 1 Connect the L Live wire from the power supply of the auxiliary device to the C Common terminal 2 Then connect either the NC or NO contact of the relay depending on what is required for controlling the auxiliary device to the auxiliary device For example if the relay is used to cut out a ...

Page 6: ...wer 8 The green LED on the Alarm s should be on When the test button is pressed the horn should sound and the relay will switch within 10 seconds Note A maximum of 12 Alarms may be interconnected to one Relay Base When one Alarm sounds all interconnected Alarms will sound and the relay will switch Attention Do not interconnect Carbon Monoxide Alarms with Smoke Heat Alarms unless an Ei1529RC contro...

Page 7: ... power then contact us at the nearest address given at the end of this manual If you are advised to return your Relay Base please ensure that it is placed in a padded box that the slide switch for the rechargeable cells is on the OFF position Ei128RBU only and include the proof of purchase and a note stating the nature of the fault Ei Electronics guarantees the Relay Bases for five years from date...

Page 8: ...nics com The crossed out wheelie bin symbol that is on your product indicates that this product should not be disposed of via the normal household waste stream Proper disposal will prevent possible harm to the environment or to human health When disposing of this product please separate it from other waste streams to ensure that it can be recycled in an environmentally sound manner For more detail...