background image

5. Connect the house wires (L-Live to wires coloured brown, 

red or marked L, N-Neutral to wires coloured blue, black or 
marked N) to the terminal block as shown in figure 1b.

NB: The unit must not be earthed so do not connect a green 
/ yellow or copper earth wire to any terminal.

6.   Connect the wires to the required relay contacts for controlling 

the auxiliary device. (The contacts are isolated and are rated 
at 250VAC, 5 amps resistive). 

If momentary relay operation is required, carefully and 
gently slide the yellow switch to the “P” position with a small 
screwdriver (see figure 1b). This is commonly used with 
warden call systems where only momentary short circuit 
signalling is required. This must be done before the mains 
power is connected or the rechargeable cells are activated.

With the switch in the “C” position, the alarm signal will 
switch the latching relay until it receives a cancel signal. 

7. Connect the rechargeable cells by carefully and gently sliding 

the switch to the “ON” position (see figure 1b). This switch 
must be in the ‘on’ position to ensure correct operation.

2

HOUSE
CODE
SWITCH

INDICATOR LIGHT

GREEN - MAINS
RED - LOW BATTERY
RED - HOUSE CODING

COVER ATTACHMENT

SCREWS

Figure 1a

RECHARGEABLE

CELLS

ON/OFF

SLIDE SWITCH

HOUSE CODE

 SWITCH

C - CONTINUOUS RELAY

RELAY CHANGES

FOR 5 SECONDS

P - PULSE

ANTENNA

(KEEP CABLES

AWAY)

REAR ENTRY

KNOCKOUT

INDICATOR

LIGHT

CONNECT RELAY
WIRES TO THE
TERMINAL BLOCK
NO - NORMALLY OPEN
NC - NORMALLY CLOSED
C - COMMON

(DOUBLE INSULATE ALL WIRES)

SURFACE
CONDUIT
CABLE
ENTRY

SCREW

MOUNTING

HOLES

ON

OFF

NO

N
IC
L
L
IC
N

NC

C

CONNECT MAINS
TO TERMINAL BLOCK
L - LIVE
N - NEUTRAL

P

C

Figure 1b

Summary of Contents for RadioLINK Relay Module Ei428

Page 1: ...7671 Failure to install the unit correctly may expose the user to shock or fire hazards This unit is not waterproof and must not be exposed to dripping or splashing The Ei428 must only be installed in a building installation where an appropriate disconnect device has been fitted i e all pole mains switch 1 Choose a suitable mounting position near the mains supply and the device to be connected to ...

Page 2: ...he mains power is connected or the rechargeable cells are activated With the switch in the C position the alarm signal will switch the latching relay until it receives a cancel signal 7 Connect the rechargeable cells by carefully and gently sliding the switch to the ON position see figure 1b This switch must be in the on position to ensure correct operation 2 HOUSE CODE SWITCH INDICATOR LIGHT GREE...

Page 3: ...esult in 4 flashes It may take up to 10 minutes before all 4 flashes are seen The flash pattern will repeat every 5 to 10 seconds while the Ei428 remains in house code mode If it fails to flash the correct number of times then consult the Troubleshooting section of this instruction manual To complete the commissioning the RF system must exit House Code mode 13 The Ei428 will automatically exit Hou...

Page 4: ...ck that all detectors relays are communicating in their final installed positions If units are rotated and or resited we recommend that all units are returned to the factory settings press and hold the house code switch on for about 6 seconds until the relevant light comes on and then flashes slowly Then house code all units again in their final positions as indicated above The RadioLink interconn...

Page 5: ...elay should become defective within the guarantee period it must be returned to where it was purchased or alternatively to Ei Electronics carefully packaged with the problem clearly stated see section 5 Getting your Relay Base Serviced along with proof of the date of purchase We shall at our discretion repair or replace the faulty unit 7 Technical Specification Mains 230 VAC 40mA 50HZ 0 8W Mains I...

Page 6: ...ources of interference preventing communication The radio paths may be disrupted by moving furniture or renovations and so regular testing protects against these and other faults ii Receivers may be blocked by radio signals occurring on or near their operating frequencies regardless of the house coding This equipment generates uses and can radiate radio frequency energy and if not installed and us...

Page 7: ...m other waste streams to ensure that it can be recycled in an environmentally sound manner For more details on collection and proper disposal please contact your local government office or the retailer where you purchased this product Hereby Ei Electronics declares that this Ei428 RadioLINK Relay Base is in compliance with the essential requirements and other relevant provisions of Directive 2014 ...

Page 8: ...s 2020 Aico Ltd Mile End Business Park Maesbury Road Oswestry Shropshire SY10 8NR U K Tel 01691 664100 www aico co uk Ei Electronics Shannon Industrial Estate Shannon Co Clare Ireland Telephone 353 61 471277 www eielectronics com 8 ...

Reviews: