The zero for the Di
ff
eren al Pressure sensor will not be changed
in regards to the QVT’s output un l the Zero Procedure has
been completed.
ZERO FAILURE:
The Di
ff
eren al Pressure can not be zeroed if the
pressure is outside of the designated Zero range (+/
‐
0.01 in WC
or 0.25 mmWC). If the Di
ff
eren al Pressure is outside this range
and the Zero Procedure is a empted, the Procedure will Fail and
this failure will be signi
fi
ed by
fl
ashing between the Failure
Screen (Screen #1) and the Greater than 0.01 inWC Screen
(Screen #2). The original zero value will be retained.
PLEASE NOTE: Typically, the transmi er will not need to be zeroed unless the zero error ex
‐
ceeds 1 part in 1000 of the full scale of the transmi er. If the full range of the transmi er is
used, for example, then 8.00 inwc / 1000 = 0.008 in WC. The transmi er would only need to
be zeroed, then, if the zero error is greater than 0.008 inWC.
#1
#2