INSTALLATION
POSITIONING:
Position the dehumidifier unit in the center of the room to be conditioned if at
all possible. However if a damp patch is particularly apparent the outlet grille
should be pointed towards it.
NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have
clear space around them and not be obstructed in anyway. For correct
installation and operation the unit inlet and outlet must have a clearance of
0.5M from all adjacent surfaces and or structures.
WIRING:
Connect the power cord of the dehumidifier to a suitable single phase, fused
power supply. As follows:-
Brown
Live
Blue
Neutral
Green/Yellow
Earth (ground)
ALARM WIRING:
Plug L (Normally Open Contacts)
Plug N (Close on Humidity Rise)
Plug E (Earth)
DRAINAGE:
Connect a 15mm inside diameter hose to the condensate outlet pipe
(positioned centrally, beneath the air inlet grille). Secure the hose using a
worm drive clip. The hose should at no point be raised higher than the outlet
pipe. The hose should be ran to a permanent drain. Failure to observe this
requirement will result in flooding of the dehumidifier unit. Ensure the drain
tube heater tape is inserted the full length of the drain tube.
OPTIONAL
The CD100 may also be fitted with a water pump capable of discharging the
condensate a vertical height of 30ft. The water can, therefore, be discharged
into a drain some distance away.