Page 8 of 16
Drawing : - TPC181
Issue
: - 11
Date
: - 24/11/16
SPECIAL FEATURES
HEATED CONDENSATE DRAINAGE TUBE:
The CD100E dehumidifier is fitted with a heater tape which runs the length of
the condensate tube. The effect of this heated condensate drainage tube will
ensure that the drainage point for the dehumidifier is kept free from ice when
operated in low ambients.
CONTROL AND ALARM HUMIDISTAT:
The CD100E has 2 Humidistats Fitted:
Adjustable Humidistat
This humidistat incorporates a knob / pointer and a graduated scale which
gives the customer the facility to select the desired humidity level within the
room being dried. The humidistat is positioned behind the front cover; this
removes the Humidistat from normal view and therefore reduces the
possibility of being mistakenly adjusted.
Factory Pre-Set Humidistat
The humidistat is factory pre-set at 70%. A Voltage free set of Normally Open
contacts are available at the Alarm Plug situated on the control panel. This
facility allows the customer to connect to an external Alarm Monitoring
System. The contacts will close on High RH.