Application manual
Interface for Load monitoring and control EK- CF2-TP
Revision 1.0.0 - Update: 04/07/2017
© EKINEX S.p.A.
– All rights reserved
MAEKCF2TP_IT
Pag. 20
8.5. Thresholds Y Channel X
Nome parametro
Condizioni
Valori
ThresholdY
Enable thresholds = enable
enable
disable
ValueY
ThresholdY Channel X = enable
Da 10 a 32000 W
500
Status Y
ThresholdY Channel X = enable
Negata
Not Negata
TypeY
ThresholdY Channel X = enable
Sotto
Sopra
HysteresisY
ThresholdY Channel X = enable
From 1 To 1000 W
500
Disable from bus
ThresholdY Channel X = enable
Yes
no
Disable modeY
ThresholdY Channel X = enable
inverted ( = 0 )
not inverted (=1)
Status cyclical sendingY
ThresholdY Channel X = enable
0
[values
0 s … 120 min]
Threshold activation delay
ThresholdY Channel X = enable
0 ( nessun ritardo)
[values
0 s … 240 s]
Nome oggetto
Condizioni
Dimens.
Flags
DPT
Nr. Ogg. Com.
Channel X Threshold1
Threshold1 = enable
4 byte
-WC---
[14.056]
power (W)
5,56,107,158
Channel X Threshold2
Threshold2 = enable
4 byte
-WC---
[14.056]
power (W)
6,57,108,159
Channel X Threshold3
Threshold3 = enable
4 byte
-WC---
[14.056]
power (W)
7,58,109,160
Channel X Threshold4
Threshold4 = enable
4 byte
-WC---
[14.056]
power (W)
8,59,110,161
Channel X Threshold 5
Threshold5 = enable
4 byte
-WC---
[14.056]
power (W)
9,60,111,162
Channel X Threshold 6
Threshold6 = enable
4 byte
-WC---
[14.056]
power (W)
10,61,112,163