background image

3

The device has four operating modes with setpoint values 

to be set independently for the operation in heating and 

cooling. The setpoint values as well as the using during 

the day of the various operating modes depend on a num-

ber of specific factors such as the building type, the use 

of the room, the individual perception of heat and cold, 

the ‘inertia characteristic of the room terminals, etc. and 

should be carefully considered with the planner of the he-

ating system, the customer and the user.
Comfort
The comfort operating mode is generally set when people 

occupy continuously a room.
Standby
The standby operating mode is set in case of absence 

of short duration from the room. This mode provides a 

small attenuation of the temperature compared to comfort 

mode; the attenuation assumes a different direction de

-

pending on the seasonal mode setting (lower temperature 

for heating, higher temperature for cooling).
Economy
The economy operating mode is set for example in case 

of prolonged absence from the room, during the night 

hours, etc. and provides an bigger attenuation of tempe-

rature larger than the standby mode.
Building protection
The building protection operating mode is provided with 

a temperature threshold; when exceeded, warm or cold 

conveying fluid is requested to the thermal generator to 

avoid potential damages to the building (equipment, fur-

nishings, devices) caused by too low (frost protection) or 

too high (overheating protection) internal temperatures. 

The building protection function is effective only when the 

thermal generator (boiler or chiller) is regularly operating. 

If  configured  and  connected  to  a  window  contact,  the 

device automatically switches to the building protection 

mode at the window opening and switches back to the 

previous mode at the window closing.

Mounting position

For the temperature control function the value of the room 

temperature may be measured by the temperature sen-

sor integrated in the device, by another KNX temperature 

sensor, by a temperature sensor connected to one input, 

or be calculated as a weighted average value of two dif-

ferent sources.  

Note. If the device is in the building protection 

mode, when the temperature exceeds the threshold 

setting, the valve of the hydraulic circuit is opened 

even if the fan is switched off.

i

Symbol

Fan operation

Switched off mode (OFF): the fan is switched off 

and the regulation can not activate it, indipendently 

from the the difference between the measured tem-

perature and the current temperature setpoint.
Automatic mode (A): the fan speed is automatically 

regulated depending on the difference between the 

measured temperature and the current temperature 

setpoint.

Manual mode: the fan speed is manually forced 

to the level corresponding to the number of bars  

switched on (from 1 to 5).

1,50 m

min 0,3 m

Changing operating mode

If the device is configured to operate as a slave, the set

-

ting of the operating mode is done via bus by another 

KNX device with supervising function (such as a timer or 

a centralised control and visualisation unit) of the building 

automation system. The only change of operating mode 

enabled manually is the recalling of the comfort mode 

for a configurable time interval with ETS. If the device is 

configured for stand-alone operation, the change of the 

operating mode is done manually using the rockers for 

the control of the room temperature controller functions.

Ventilation control

The device allow the control of the ventilation function. 

The regulation may be continuous or stepwise (max 3 

speed levels).

If the temperature value measured by the integrated sen-

sor is used, for an optimal temperature control the device 

must be installed taking care of:
•  installing the device on an inner wall of the room at a 

height of about 1.5 m from the floor;

• 

not shielding the device with curtains, furniture or other;

•  verifying that from the duct connected to the wall box 

does not come airflows that might affect the temperatu

-

re measurement; 

•  avoiding the installation close to heat sources (such as 

domestic appliances or lighting devices), pipes for the 

distribution of hot or cold water and terminal devices for 

heating and cooling; 

•  avoiding the installation where the device may be 

subject to direct sunlight through glass surfaces. 

If these conditions can not be satisfied, it is appropriate to 

use a weighted average value between two temperature 

values measured in the same room according to the dif-

ferent possibilities offered from the device (temperature 

sensor connected to an input or a KNX temperature sen-

sor). If a second temperature value can not be measured, 

it is also possible to correct the value measured by the 

sensor integrated in the device using the appropriate of-

fset parameter in the ETS application program. 

Mounting

The device has degree of protection IP20, and is therefo-

re suitable for use in dry interior rooms. The installation of 

the device requires the following steps:
a) 

fix the metallic support (f) with the screws supplied (e) 

on the wall box (g); 

b) 

if required, snap a square frame (d) of the form or flank 

series, inserting it from the rear of the device (b) ;

c)  connect the sensors or the contacts required to the 

4-poles screw terminal block on the rear of the device; 

d) insert the terminal for the bus (red/black), previously 

connected to the bus cable, in its slot on the rear side 

Summary of Contents for EK-EP2-TP- Series

Page 1: ...the independent ther mal regulation of a room or a zone It has to be used in KNX installations for control of homes and buildings Description The ekinex room temperature controller is a KNX S mo de device for the independent temperature regulation of a room or a zone in a building In combination with one or more KNX actuators the room temperature controller is able to control the heating and cooli...

Page 2: ...a setting 3 symbol ventilation control change of operating mode operation exit 4 minus symbol decrease of value The thermostat has an LC display with adjustable bac klight that occupies vertical ly the left half of the front side Depending on the in formation to be displayed a combination of digits and symbols can be switched on The light intensity emit ted from the display can be set during the c...

Page 3: ...lated depending on the difference between the measured temperature and the current temperature setpoint Manual mode the fan speed is manually forced to the level corresponding to the number of bars switched on from 1 to 5 1 50 m min 0 3 m Changing operating mode If the device is configured to operate as a slave the set ting of the operating mode is done via bus by another KNX device with supervisi...

Page 4: ...e environmental influences by means of an offset parameter In order to avoid that too rapid temperature fluctuations negatively affect the regulation process an acquisition filter can be set If necessary for the regula tion can be used a weighted average between the value measured by the integrated sensor and another tempera ture value measured in the room by a temperature sensor connected to one ...

Page 5: ...specialized skills To acquire these skills you should attend the workshops at KNX cer tified training centers i Commissioning For commissioning the device the following activities are required make the electrical connections as described above turn on the bus power supply switch the device operation to the programming mode by pressing the programming pushbutton located on the front side in the are...

Page 6: ...inex is a registered trademark of SBS S p A KNX and ETS are registered trademarks of KNX As sociation cvba Brussels SBS S p A 2017 The company reserves the right to make changes to this documentation without notice Marks KNX CE the device complies with the Low Voltage Directi ve 2014 35 EU and the Electromagnetic Compatibility Directive 2014 30 EU Tests carried out according to EN 50491 5 1 2010 E...

Reviews: