Note. 

When mounting the device in boards and ca-

binets it shall be provided the necessary ventilation 

so that the temperature can be kept within the ope-

rating range of the device.

i

INSTALLATION TECHNICAL NOTES

•  Installation and maintenance must be 

performed only if the power supply has 

been turned off.

•  Installation and maintenance must only 

be  performed  by  qualified  personnel  in 

compliance with current regulations.

•  The product  must  be  installed  insi-

de an electrical panel protected against 

overvoltages.

•  The product must be installed in a verti-

cal position with the front / label facing 

the front or in a horizontal position with 

the front / label facing upwards. Other 

product installation positions are not al-

lowed. The bottom position with the front 

panel / label facing down is not allowed.

•  Keep separated the circuits at 230V  and 

the circuits not SELV from circuits to low 

voltage (SELV) and from any connection 

with this product. It is absolutely forbid-

den to connect, for any reason whatsoe-

ver, directly or indirectly, the 230V mains 

voltage to the bus or to other parts of the 

circuit.

!

All  the  devices  and  the  control  signal  connected  to  the 

DALI  bus  and  to  the  local  command  (where  available) 

must be SELV (the devices connected must be SELV or 

supply a SELV signal).

Characteristics of the DALI terminal block

• 

Screw tightening of the conductors

• 

Command  and  bus  wiring:  1.5  mm

2

  solid  –  1.0  mm

2

 

stranded – 16 - 17 AWG

• 

Conductor stripping recommended: 5.0 - 6.0 mm

• 

Maximum  length  of  the  connection  between  dimmer-

driver and control device < 10 m

• 

Length of bus connection cables < 10 m

Connection of power supply and LEDs

For the power supply use SELV power suppliers with li

-

mited current, short circuit protection only and the power 

must be correctly dimensioned. In case of usage of a po

-

wer supplier with ground terminals, all points of the pro

-

tective earth (PE = Protection Earth) must be connected 

to a valid and certified protection earth.

Insert  the  mounting  support  in  the  appropriate  shaped 

profile of the back side of the device, then hook the teeth 

to the profile guide starting from the bottom. Finally, push 

the upper part towards the guide for final coupling.

DALI bus line and command connection

The  connection  to  the  DALI  bus  network  and  the  local 

commands is done via the screw terminal, located on the 

front of the device in the upper part.

For the EK-GD2-DL-1-LV device, the length of the con

-

nection cables between the local commands (if available) 

and the product must be less than 10m; the cables must 

be  correctly  dimensioned  and  they  should  be  isolated 

from every wiring or parts at voltage not SELV. Use dou

-

ble insulated shielded and twisted cables.

The length and type of the connection cables to the DALI 

bus must be compliant with the protocol specification and 

the present regulations and they should be isolated from 

every wiring or parts at voltage not SELV. Use double in

-

sulated shielded and twisted cables.

Installation scheme for EK-GD2-DL-1-LV

Installation scheme for EK-GD2-DL-2-LV

Setup and installation

The steps for installing the device are as follows:

• 

connect the loads to the “LED OUT” output terminals 

of the device;

• 

for the EK-GD2-DL-1-LV model, connect the local com

-

mand to the “PUSH” input if you want to use the “stand-

alone” mode;

• 

connect the DALI bus to the related DA terminal blocks;

• 

connect  the  12/48  Vdc  power  supply  to  the  terminal 

blocks “DC IN” of the device.

All  the  devices  and  the  control  signal  connected  to  the 

DALI  bus  and  to  the  local  command  (where  available) 

must be SELV (the devices connected must be SELV or 

supply a SELV signal).

Summary of Contents for EK-GD2-DL-1-LV

Page 1: ...a single DT6 output channel 2 single DT6 channels or a single chan nel in TW DALI DT8 mode DT6 DT8 setting for EK GD2 DL 2 LV model is done via local selector switch The devices have an integrated bus communication module DALI 2 certified Technical data Inputs Input constant voltage 12 48 Vdc Supply voltage min 10 8 Vdc max 52 8 Vdc Power absorbed while awaiting command 500 mW for EK GD2 DL 1 LV o...

Page 2: ...k or DT6 DT8 selector 5 PUSH N O pushbutton pole 1 PUSH N O pushbutton pole 2 EK GD2 DL 1 LV only EK GD2 DL 2 LV only Accessory for 1 CH and 2 CH models Rail mounting support The devices EK GD2 DL 1 LV and EK GD2 DL 2 LV can be mounted on 35 mm rail according to EN 60715 with the plastic support included in the delivery Control signaling and connection elements The devices are equipped with screw ...

Page 3: ...hort circuit protection only and the power must be correctly dimensioned In case of usage of a po wer supplier with ground terminals all points of the pro tective earth PE Protection Earth must be connected to a valid and certified protection earth Insert the mounting support in the appropriate shaped profile of the back side of the device then hook the teeth to the profile guide starting from the...

Page 4: ...ue to indicate the programming of the outputs as 2 single channels DALI DT6 pressing the button again will cause the yellow LED to light up indicating that the programming of the outputs is in Tunable White dynamic white with 1 DALI DT8 channel with a long press of at least 5 s the configuration is saved and the menu is exited after 60 s without further pressing the programming key the device exit...

Page 5: ...n on the DALI bus update the device The software can be downloaded from the website www ekinex com and its use is described in the application ma nual of the ekinex EK BG1 TP DALI Gateway The sof tware works with Microsoft Windows 7 and later DT6 with single output channel DT6 with 2 independent output channels DT8 with single Tunable White output channel DALI System fail function For each device ...

Page 6: ...ranty period In case of tampering the compliance with the essential requirements of the applicable directives for which the device has been certified is no longer guaranteed ekinex defective devices must be returned to the ma nufacturer at the following address Ekinex S p A Via Novara 35 I 28010 Vaprio d Agogna NO Italy Other information The instruction sheet must be delivered to the end cu stomer...

Reviews: