background image

4

signal on the DALI bus and immediately use the fade, 

otherwise the switching on and off would be immediate.

• 

Advanced function (blue status LED): using a DALI pro

-

grammer such as USB DALI interface Tridonic, Lunato

-

ne DALI Cockpit or similar, it is possible to program the 

parameters System Fail Level = 100% and Fade Time 

= 0, according to the DALI specifications.

The  connection  cables  between  the  power  source  “low 

voltage” and the product must be correctly dimensioned 

and they should be isolated from every wiring or parts at 

not-SELV voltage. Use double insulated cables.

The  power  supply  must  be  dimensioned  according  to 

the load connected to the device. If the power supply is 

oversized with respect to the maximum absorbed current, 

then insert a protection against over-current between the 

power supply and the device.

Characteristics of the supply and LEDs terminal block

• 

Screw tightening of the conductors

• 

Power and LEDs wiring: 1.5 mm

2

 solid – 1.0 mm

2

 stran

-

ded – 16 - 17 AWG

• 

Power and LEDs stripping recommended approx.: 5.0 

- 6.0 mm

• 

Max torque 0.5 Nm

Outputs

The length of the connection cables between the product 

and the LED modules must be less than 10 m; the cables 

must be dimensioned correctly and must be isolated from 

any  wiring or parts with  non-SELV voltage.  Use  double 

insulated shielded and twisted cables.

If you want to use connection cables between the product 

and the LED modules over 10m, the installer must ensure 

the proper functioning of the system. In any case, the con

-

nection between the product and the LED modules must 

not exceed 30 m.

A further long press of the programming button for at least 

5 seconds confirms the setting of the selected function.
The device will always work in both modes: the default or 

advanced programming only sets the DALI System Fail 

Level and Fade Time parameters without the need for a 

DALI programmer.

EK-GD2-DL-2-LV programming
The device is equipped with a programming button on the 

front, near the DA terminals, to select the DALI DT6 / DT8 

configuration of the channels.

While the status LED is on, a long press of the program

-

ming button for at least 5 s allows you to enter program

-

ming mode and the LED flashes.

At this point:

• 

by pressing the button once, the LED lights up purple, 

to indicate the programming of both outputs as a single 

DALI DT6 channel;

• 

by pressing the button again, the LED lights up blue, 

to indicate the programming of the outputs as 2 single 

channels DALI DT6;

• 

pressing the button again will cause the yellow LED to 

light up, indicating that the programming of the outputs 

is in Tunable White (dynamic white) with 1 DALI DT8 

channel;

• 

with  a  long  press  of  at  least  5  s  the  configuration  is 

saved and the menu is exited;

• 

after 60 s without further pressing the programming key, 

the device exits the menu without saving the setting.

Courtesy light function (EK-GD2-DL-1-LV) only)
When the output is off, a long press of the local control 

button  for  at  least  0.7  s  turns  on  the  load  at  minimum 

intensity for 2 s, then starts dimming towards maximum 

intensity. If the button is released at this stage, the bright

-

ness level stops.

Configuration and commissioning

Configuration and commissioning activities of the device 

must be carried out according to the design of the building 

automation system done by qualified planners.

For commissioning the device the following activities are 

required: 

• 

make the electrical connections as indicated above;

• 

power up the bus;

• 

for EK-GD2-DL-1-LV device, it is possible to select the 

“stand-alone” mode through the local command (con

-

nection to the DALI bus is not necessary);

• 

carry out the device programming, as described below.

EK-GD2-DL-1-LV programming
At the first start-up, in case of lack of the DALI bus, the 

local control is active and the LED placed under the front 

programming key is orange. When the presence of the 

DALI bus is detected, control passes to it. In the absence 

of the DALI bus, control passes to local control by pres

-

sing the button.
Button behavior:

• 

Short press: on / off function;

• 

Long press: reverses the direction of dimming.

The device is equipped with a programming button on the 

front, near the DA terminal: by pressing the programming 

button for 5 seconds, the status LED starts flashing. Pres

-

sing the button again allows you to select the function of 

the device:

• 

Default function (orange status LED): sets the System 

Fail Level parameter = 100% and the Fade Time = 0.7 

s), to make the device work even in the absence of a 

Note. 

If the dimmer is used together with a bro-

adcast DALI device, depending on the implemen-

tation of the firmware, the broadcast function may 

prevail over the local command.

i

Note. 

The programming of the parameters men-

tioned above must be carried out only during the 

programming phase. If the customer has a DALI 

programmer / master, he can reprogram them as 

he wishes.

i

The setting of the output channels can also be done using 

DALI programmers. An example is shown in the next fi

-

gures.

Summary of Contents for EK-GD2-DL-1-LV

Page 1: ...a single DT6 output channel 2 single DT6 channels or a single chan nel in TW DALI DT8 mode DT6 DT8 setting for EK GD2 DL 2 LV model is done via local selector switch The devices have an integrated bus communication module DALI 2 certified Technical data Inputs Input constant voltage 12 48 Vdc Supply voltage min 10 8 Vdc max 52 8 Vdc Power absorbed while awaiting command 500 mW for EK GD2 DL 1 LV o...

Page 2: ...k or DT6 DT8 selector 5 PUSH N O pushbutton pole 1 PUSH N O pushbutton pole 2 EK GD2 DL 1 LV only EK GD2 DL 2 LV only Accessory for 1 CH and 2 CH models Rail mounting support The devices EK GD2 DL 1 LV and EK GD2 DL 2 LV can be mounted on 35 mm rail according to EN 60715 with the plastic support included in the delivery Control signaling and connection elements The devices are equipped with screw ...

Page 3: ...hort circuit protection only and the power must be correctly dimensioned In case of usage of a po wer supplier with ground terminals all points of the pro tective earth PE Protection Earth must be connected to a valid and certified protection earth Insert the mounting support in the appropriate shaped profile of the back side of the device then hook the teeth to the profile guide starting from the...

Page 4: ...ue to indicate the programming of the outputs as 2 single channels DALI DT6 pressing the button again will cause the yellow LED to light up indicating that the programming of the outputs is in Tunable White dynamic white with 1 DALI DT8 channel with a long press of at least 5 s the configuration is saved and the menu is exited after 60 s without further pressing the programming key the device exit...

Page 5: ...n on the DALI bus update the device The software can be downloaded from the website www ekinex com and its use is described in the application ma nual of the ekinex EK BG1 TP DALI Gateway The sof tware works with Microsoft Windows 7 and later DT6 with single output channel DT6 with 2 independent output channels DT8 with single Tunable White output channel DALI System fail function For each device ...

Page 6: ...ranty period In case of tampering the compliance with the essential requirements of the applicable directives for which the device has been certified is no longer guaranteed ekinex defective devices must be returned to the ma nufacturer at the following address Ekinex S p A Via Novara 35 I 28010 Vaprio d Agogna NO Italy Other information The instruction sheet must be delivered to the end cu stomer...

Reviews: