background image

PILOT ASSEMBLY

Clean the pilot assembly with a soft brush and blow through.  Check the aeration holes are free of any dirt
or lint.  Clean thoroughly internally, the connection can be removed from the base of the pilot unit using
two spanners to make cleaning easier.  Do not damage or try to dismantle the pilot injector.

The unit is factory set and the only check necessary is to ensure the spark gap is correct.  See specifica-
tions for gas setting.

NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT

. If the pilot will not

stay lit there is a problem with dirt, the gas supply, or the thermocouple needs replacement. Modifications
are dangerous and can have a serious unseen effect on safety and therefore MUST not be done.
Replacements must be original manufacturers parts. Re-assemble in the reverse of removal. Ensure setting
pressures are as stated in Section 2; Appliance Data.

CATALYST

It is recommended that the catalysts are inspected for signs of damage and dirt during routine servicing
procedures. The expected life of the catalysts is in excess of 11,000 hours (10 years of normal use).  After
this time the catalysts should be replaced.

If there are any deposits of dirt or soot on the catalyst they should be cleaned with a soft brush and a vac-
uum cleaner. If removed for cleaning ensure the seals are in good condition before replacing the catalyst.
New seals will usually be required. The performance of the catalysts may be checked using a combustion
gas analyser as follows. Any analyser used should conform to EN 50379-3. 

Ignite the fire as per the operating instructions, and run at maximum setting for 15 minutes. Position gas
sample probe directly over the catalysts via the outlet grille, on top of the appliance. Record the carbon
dioxide (CO2) concentration and then the carbon monoxide (CO) concentration as displayed by the analyser

- also noting the units in which the values are expressed.  Most analysers display carbon dioxide (CO2) con-

centrations in percentage (%) terms and carbon monoxide concentration in parts per million (ppm) terms.

In order to calculate the combustion ratio for the appliance (CO/CO2) it is first necessary to express both

gas concentrations in terms of percentage. To convert from parts per million (ppm) to a percentage (%)
divide the ppm figure by 10,000. Examples : 35ppm = 0.0035%, 15ppm = 0.0015%, 5ppm = 0.0005%. Now
divide the concentration of carbon monoxide (CO) expressed in percent by the concentration of carbon
dioxide (CO2) to obtain the appliance combustion ratio.

The combustion ratio of the gasses emitted by the catalytic convertor should not exceed 0.0015.

If replacing, firstly, remove the decorative frame/glass facia (as described in section 8.3) and outer casing.
The catalysts are located on the top of the internal firebox and can be removed by unscrewing the retain-
ing nuts securing the clamping plates. Remove the catalysts their seals and discard. Refit the new catalysts
and seals in reverse order, ensure the catalysts and the glass door have good seals.  

TESTING FOR FIREBOX LEAKAGE

Appliances that are several years old or have been extensively dismantled should be checked for sound-
ness. It is important that all the products of combustion pass through the catalytic converter at the top of
the firebox before leaving the appliance. 

The firebox is heated by lighting for a few minutes to provide a flow through the firebox. The burner is
then shut off and a smoke pellet or match introduced at the base of the fire underneath the burner tray.
Large quantities of smoke will emerge from the top of the appliance, but none should emerge from the
joints or gasket faces, especially around the door. 

It is important to note that the appliance can never be expected to be 100% smoke tight and small quan-
tities of smoke may be seen in corners of joints and gasket faces etc without affecting safety when the
fire is in operation.

9

CO (%)
CO2 (%) = ratio

10.4

10.3

10.2

©

2009 Focal Point Fires plc.

Summary of Contents for eko 5010

Page 1: ...user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 5010 eko 5020 eko 5030 eko 5040 fuel effect gas fire manual remote contro...

Page 2: ...Eko 5010 Eko 5020 Eko 5030 Eko 5040 2009 Focal Point Fires plc...

Page 3: ...convert from cubic feet ft3 to cubic metres m3 divide the room vol ume in ft3 by 35 3 This appliance is intended as a secondary source of heat only and should not be used in a room without some form...

Page 4: ...background heat ing present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room On first light up of a new appliance burning o...

Page 5: ...om size in cubic metres m3 divide the room volume in cubic feet ft3 by 35 3 SITE REQUIREMENTS This appliance is designed to be wall hung Do not recess any part of the appliance into the wall This appl...

Page 6: ...s should be positioned on the wall above the appliance It should be established that any mirrors or picture frames etc to be positioned on the wall above the appliance are able to withstand prolonged...

Page 7: ...connections may be made using the entry points in the bottom or sides of the firebox A concealed gas connection may be made using the knock out hole in the centre back of the firebox Select the most...

Page 8: ...For further guidance for wall fixing in tim ber framed buildings refer to any relevant local codes of practice Flat Wall Fixing All Models To assist with fixing the appliance a template is provided a...

Page 9: ...spark There should be no need to adjust this If under any circumstances the piezo electric spark fails the pilot cannot be lit manually SETTING PRESSURE The pressure test point is located on the left...

Page 10: ...g Ensure each screw is u n s c r e w e d approximate ly one turn from the fully screwed in position in order to cre ate a 2mm gap shown in figure 10 Simply hang the facia panel onto the outer casing f...

Page 11: ...13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instructions see relevant sectio...

Page 12: ...noting the units in which the values are expressed Most analysers display carbon dioxide CO2 con centrations in percentage terms and carbon monoxide concentration in parts per million ppm terms In ord...

Page 13: ...as a hole holes through which there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or...

Page 14: ...als or flooring should protrude onto the hearth if fitted This appliance incorporates a combustion monitoring system ODS DO NOT burn any foreign material on this fire Under no circumstances shall the...

Page 15: ...local Codes and or Regulations Ventilation fitted under or within immediate vicinity of the appliance must not be used as it may adverse ly effect performance of the combustion monitoring system ODS...

Page 16: ...ass cleaner Test on a small area first PAINTED AREAS These can be cleaned using a dry cloth STAINLESS STEEL AREAS These can either be cleaned using a proprietary stainless steel metal cleaner or baby...

Reviews: