background image

TROUBLESHOOTING GUIDE

Fire sparks but pilot does not light

• 

No gas to fire, check isolators are open and gas supply is on.

• 

Pipework blockage, clean out.  

• 

Air not fully purged, re purge supply or wait longer.  

• 

Spark earthing to metalwork, reset gap correctly.  

• 

Blocked pilot, clean out internally.

Pilot lights but then goes out

• 

Severe restriction in gas supply: clear obstruction.  

• 

Faulty thermocouple, replace pilot unit.  

• 

Blocked pilot, clean out. 

• 

Blocked lint gauze, clean. 

• 

Hold control knob in for longer. 

• 

Check control knob does not foul indicator plate.

• 

If the pilot will not stay lit there could be a problem with contami

nation of the gas supply, drafts, room size and/or ventilation or  
the thermocouple needs replacement.

Modifications are dangerous and can have a serious unseen effect on safety. 

NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT.

Fire does not spark at pilot

• 

HT lead detached, refit.  

• 

Check the spark gap (see section 8.2).

• 

Faulty piezo unit, replace.  

• 

Debris shorting out electrode, clean.  

• 

Spark shorting to metalwork under tray, check routing of HT lead under burner.

Fire runs for a time 

• 

Loose or faulty thermocouple, rectify. 

and then cuts off

• 

Blocked pilot, clean out. 

• 

Fire is sited in a draft.

• 

Door or window has been opened creating a draft.

• 

Wall on which fire is sited has a hole/holes through which there is a draft.

• 

Fire is too close the an air vent.

• 

Fire is sited on disused chimney breast which has not been adequately sealed up.

• 

Dirt or lint in pilot aeration hole or on the lint gauze, clean thoroughly. 

• 

If the pilot will not stay lit there could be a problem with contami

nation of the gas supply, drafts, room size and/or ventilation or  
the thermocouple needs replacement.

Modifications are dangerous and can have a serious unseen effect on safety. 

NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT.

Pilot flame shrinks when 

• 

Poor gas flow to fire, check pressure with fire on high.  

fire is on high

• 

If pressure is low, remove any restriction in pipework or valve.

• 

Check all isolators are adequately sized and fully open. 

• 

Check meter pressure is adequate. 

• 

If the pilot will not stay lit there could be a problem with contami

nation of the gas supply, drafts, room size and/or ventilation or  
the thermocouple needs replacement.

Modifications are dangerous and can have a serious unseen effect on safety. 

NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT.

Fire smells when first lit or in use

• 

Newness smell from brand new appliance.  

• 

Leakage occurring.  Carry out leakage test and rectify any problems. 

• 

Combustible materials used in incorrect positions.

• 

Airborne substances such as cleaning materials/air fresheners 

are being drawn through the fire.

Other airborne contaminants such as dust, tobacco smoke, paint vapours.

10

11.0

©

2009 Focal Point Fires plc.

Summary of Contents for eko 5010

Page 1: ...user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 5010 eko 5020 eko 5030 eko 5040 fuel effect gas fire manual remote contro...

Page 2: ...Eko 5010 Eko 5020 Eko 5030 Eko 5040 2009 Focal Point Fires plc...

Page 3: ...convert from cubic feet ft3 to cubic metres m3 divide the room vol ume in ft3 by 35 3 This appliance is intended as a secondary source of heat only and should not be used in a room without some form...

Page 4: ...background heat ing present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room On first light up of a new appliance burning o...

Page 5: ...om size in cubic metres m3 divide the room volume in cubic feet ft3 by 35 3 SITE REQUIREMENTS This appliance is designed to be wall hung Do not recess any part of the appliance into the wall This appl...

Page 6: ...s should be positioned on the wall above the appliance It should be established that any mirrors or picture frames etc to be positioned on the wall above the appliance are able to withstand prolonged...

Page 7: ...connections may be made using the entry points in the bottom or sides of the firebox A concealed gas connection may be made using the knock out hole in the centre back of the firebox Select the most...

Page 8: ...For further guidance for wall fixing in tim ber framed buildings refer to any relevant local codes of practice Flat Wall Fixing All Models To assist with fixing the appliance a template is provided a...

Page 9: ...spark There should be no need to adjust this If under any circumstances the piezo electric spark fails the pilot cannot be lit manually SETTING PRESSURE The pressure test point is located on the left...

Page 10: ...g Ensure each screw is u n s c r e w e d approximate ly one turn from the fully screwed in position in order to cre ate a 2mm gap shown in figure 10 Simply hang the facia panel onto the outer casing f...

Page 11: ...13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instructions see relevant sectio...

Page 12: ...noting the units in which the values are expressed Most analysers display carbon dioxide CO2 con centrations in percentage terms and carbon monoxide concentration in parts per million ppm terms In ord...

Page 13: ...as a hole holes through which there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or...

Page 14: ...als or flooring should protrude onto the hearth if fitted This appliance incorporates a combustion monitoring system ODS DO NOT burn any foreign material on this fire Under no circumstances shall the...

Page 15: ...local Codes and or Regulations Ventilation fitted under or within immediate vicinity of the appliance must not be used as it may adverse ly effect performance of the combustion monitoring system ODS...

Page 16: ...ass cleaner Test on a small area first PAINTED AREAS These can be cleaned using a dry cloth STAINLESS STEEL AREAS These can either be cleaned using a proprietary stainless steel metal cleaner or baby...

Reviews: