background image

SITE REQUIREMENTS (continued)

Clearances to non-combustibles

Non combustible surfaces are defined as brick, metal, marble, concrete etc. and also a number of man-made mate-
rials impervious to flame. If in doubt refer to the material manufacturer for further information before proceed-
ing with installation.

Clearances to the sides of the appliance are 100mm (4in). Clearance to the front of the appliance is 500mm (20in). 

The back of the appliance may be installed directly onto a non-combustible wall, providing the area behind the
appliance is flat and does not interfere with the various vent holes in the back panel of the appliance.

A non combustible shelf of any depth may be positioned above the appliance provided it is no closer than 400mm
from the top of the appliance glass panel and the wall above the appliance is non combustible.

The appliance must not be positioned vertically within 60mm of a solid floor (i.e. wood or stone) or hearth. This
dimension is measured vertically to the bottom of the appliance firebox.

Clearances to combustible materials

Combustible materials are defined as wood, fabrics, or other materials likely to combust if exposed to flame.
Generally, any material, which is likely to discolour, melt or misshape when exposed to moderate heat, should be
considered as a combustible material or surface. 

Clearance to the sides of the appliance are 100mm(4in) but curtains, drapes and other fabrics are not permitted
within a distance of 500mm(20in) of the appliance sides. No such materials are permitted directly above the appli-
ance regardless of distance. 

The minimum clearance to the ceiling above the appliance is 800mm measured from the top of the appliance
glass panel.

Combustible materials should not be positioned directly in front of the appliance within a distance of one metre.

Under no circumstances should any electrical equipment e.g. plasma screen TV sets etc. be positioned on the wall
above the appliance. The appliance is designed to be wall mounted alone and not in conjunction with any type of
combustible fire surround. No combustible shelves should be positioned on the wall above the appliance. It
should be established that any mirrors or picture frames etc. to be positioned on the wall above the   appliance
are able to withstand prolonged exposure to moderate heat and moisture before proceeding with their installa-
tion.

The back of the appliance may be installed directly onto a combustible wall, providing it is relatively flat and
does not interfere with the various vent holes in the back panel of the appliance. The wall must be structurally
sound and constructed from a material capable of withstanding moderate heat. Brick, concrete, finished plaster,
most types of conventional wall paper and dry-lined plasterboard are usually examples of suitable materials,
however as there are many methods of wall construction and many variations in the composition of construc-
tion materials, in some circumstances, cracking may occur to plasterwork. Materials such as flock, blown vinyl
and embossed paper which are sensitive to even small amounts of heat should be avoided as scorching and or
discolouration may occur over time. Avoid siting the appliance near joins or joints in plasterboard as exposure
to moderate heat may cause cracking along the joint line.

If the appliance is to be mounted on a dry lined wall or a timber framed construction wall then the integrity and
ability of the wall to carry the weight of the appliance must be confirmed. It is important in these circumstances
that any vapour control barrier is not damaged, and that any structural members of the house frame are not dam-
aged.

The appliance must not be positioned vertically within 100 mm of a carpeted floor, rugs or fabric materials of any
kind. This dimension is measured vertically to the bottom of the appliance firebox.

VENTILATION

A minimum of 100 cm

2

purpose provided ventilation is required for this appliance. This may be achieved

either with one vent 100 cm

2

at a high or low position in the room, or split ventilation i.e. 50cm

installed

at high level and 50cm

installed at low level within the room.  An openable window or equivalent is also

required. The requirements of other flued appliance operating in the same room or space must be taken
into consideration when assessing ventilation. 

3

4.0

4.1

©

2009 Focal Point Fires plc.

Summary of Contents for eko 5010

Page 1: ...user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 5010 eko 5020 eko 5030 eko 5040 fuel effect gas fire manual remote contro...

Page 2: ...Eko 5010 Eko 5020 Eko 5030 Eko 5040 2009 Focal Point Fires plc...

Page 3: ...convert from cubic feet ft3 to cubic metres m3 divide the room vol ume in ft3 by 35 3 This appliance is intended as a secondary source of heat only and should not be used in a room without some form...

Page 4: ...background heat ing present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room On first light up of a new appliance burning o...

Page 5: ...om size in cubic metres m3 divide the room volume in cubic feet ft3 by 35 3 SITE REQUIREMENTS This appliance is designed to be wall hung Do not recess any part of the appliance into the wall This appl...

Page 6: ...s should be positioned on the wall above the appliance It should be established that any mirrors or picture frames etc to be positioned on the wall above the appliance are able to withstand prolonged...

Page 7: ...connections may be made using the entry points in the bottom or sides of the firebox A concealed gas connection may be made using the knock out hole in the centre back of the firebox Select the most...

Page 8: ...For further guidance for wall fixing in tim ber framed buildings refer to any relevant local codes of practice Flat Wall Fixing All Models To assist with fixing the appliance a template is provided a...

Page 9: ...spark There should be no need to adjust this If under any circumstances the piezo electric spark fails the pilot cannot be lit manually SETTING PRESSURE The pressure test point is located on the left...

Page 10: ...g Ensure each screw is u n s c r e w e d approximate ly one turn from the fully screwed in position in order to cre ate a 2mm gap shown in figure 10 Simply hang the facia panel onto the outer casing f...

Page 11: ...13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instructions see relevant sectio...

Page 12: ...noting the units in which the values are expressed Most analysers display carbon dioxide CO2 con centrations in percentage terms and carbon monoxide concentration in parts per million ppm terms In ord...

Page 13: ...as a hole holes through which there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or...

Page 14: ...als or flooring should protrude onto the hearth if fitted This appliance incorporates a combustion monitoring system ODS DO NOT burn any foreign material on this fire Under no circumstances shall the...

Page 15: ...local Codes and or Regulations Ventilation fitted under or within immediate vicinity of the appliance must not be used as it may adverse ly effect performance of the combustion monitoring system ODS...

Page 16: ...ass cleaner Test on a small area first PAINTED AREAS These can be cleaned using a dry cloth STAINLESS STEEL AREAS These can either be cleaned using a proprietary stainless steel metal cleaner or baby...

Reviews: