background image

TESTING AND COMMISSIONING

Turn on and test the gas supply up to the fire for any leaks, in accordance with the current edition of BS
6891 (natural gas installations) or the current edition of BS 5482 pt1 (propane installations).
For Republic of Ireland, reference should be made to the current edition of IS813 (the relevant standards
governing installation).

OPERATING THE APPLIANCE

The pilot is visible behind the left hand side of the burner.

The control knob is located on the lower right hand side of the
outer case. It is of a spherical design and is marked as shown in
figure 6;

Push in and turn the control knob to the SPARK position, and hold
there for a few seconds. Continue turning anti-clockwise through
the spark click to the PILOT light position, ensuring the pilot has
lit. If not, return the knob clockwise, and repeat.

When the pilot lights after the spark, keep the knob depressed for
approximately ten seconds. Now release the knob and the pilot
should stay alight. If the pilot is extinguished during use, wait
three minutes before repeating the ignition procedure. 

To achieve the HIGH setting, push the control knob in slightly and continue turning anti-clockwise to the
high position. The main burner should light after a few seconds.  To decrease the setting to LOW, turn the
control knob clockwise to the low setting.

To turn to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to the
pilot position and release. To turn the fire OFF, keep the knob pressed in, return to the off position and
release.

SPARK FAILURE 

The gap between the spark electrode and the pilot should be 3 - 5mm to produce a good spark.  There
should be no need to adjust this.  If under any circumstances the piezo electric spark fails, the pilot cannot
be lit manually.

SETTING PRESSURE

The pressure test point is located on the left hand side of the appliance, on the main burner pipe, next to
the brass restrictor/connector. Release the setting pressure test point screw, and attach a pressure gauge.
Light the fire on the HIGH setting.

To commission the appliance, the burner pressure must be in accordance with the figures stated in the data
section of these instructions. 

The fire is factory set to achieve these pressures and
any significant variation could indicate a supply prob-
lem. If the pressure is too high, the gas supply meter
/regulator may be set incorrectly.  This should be
checked with the fire running and if necessary reset by
the gas supplier.

If the burner pressure is too low, then check the inlet
pressure with the appliance running.  If this is less
than than  the figure stated in section 2.0 of these
instructions it will need to be reset by the gas suppli-
er. If the setting pressure is too low, but the meter
pressure is acceptable, then a problem in the supply
pipework is to be suspected.  

This will be dirt and debris, kinked or inadequate size pipes, restriction in a fitting, shut off elbow not fully
open or solder flashing across a joint. Identify the cause of the restriction and rectify. Switch the fire off,
disconnect the pressure gauge and refit the test nipple screw. Light the fire and check for gas soundness. 

In the event that the burner pressure is not in accordance with the figures stated in the data section of these
instructions, the appliance must not be commissioned, and the manufacturer should be contacted for guid-
ance.

6

8.3

8.0

8.1

8.2

‘OFF’ position

‘SPARK’ position

‘LOW’ position

‘HIGH’ position

©

2009 Focal Point Fires plc.

Figure 6

Figure 7

Summary of Contents for eko 5010

Page 1: ...user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 5010 eko 5020 eko 5030 eko 5040 fuel effect gas fire manual remote contro...

Page 2: ...Eko 5010 Eko 5020 Eko 5030 Eko 5040 2009 Focal Point Fires plc...

Page 3: ...convert from cubic feet ft3 to cubic metres m3 divide the room vol ume in ft3 by 35 3 This appliance is intended as a secondary source of heat only and should not be used in a room without some form...

Page 4: ...background heat ing present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room On first light up of a new appliance burning o...

Page 5: ...om size in cubic metres m3 divide the room volume in cubic feet ft3 by 35 3 SITE REQUIREMENTS This appliance is designed to be wall hung Do not recess any part of the appliance into the wall This appl...

Page 6: ...s should be positioned on the wall above the appliance It should be established that any mirrors or picture frames etc to be positioned on the wall above the appliance are able to withstand prolonged...

Page 7: ...connections may be made using the entry points in the bottom or sides of the firebox A concealed gas connection may be made using the knock out hole in the centre back of the firebox Select the most...

Page 8: ...For further guidance for wall fixing in tim ber framed buildings refer to any relevant local codes of practice Flat Wall Fixing All Models To assist with fixing the appliance a template is provided a...

Page 9: ...spark There should be no need to adjust this If under any circumstances the piezo electric spark fails the pilot cannot be lit manually SETTING PRESSURE The pressure test point is located on the left...

Page 10: ...g Ensure each screw is u n s c r e w e d approximate ly one turn from the fully screwed in position in order to cre ate a 2mm gap shown in figure 10 Simply hang the facia panel onto the outer casing f...

Page 11: ...13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instructions see relevant sectio...

Page 12: ...noting the units in which the values are expressed Most analysers display carbon dioxide CO2 con centrations in percentage terms and carbon monoxide concentration in parts per million ppm terms In ord...

Page 13: ...as a hole holes through which there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or...

Page 14: ...als or flooring should protrude onto the hearth if fitted This appliance incorporates a combustion monitoring system ODS DO NOT burn any foreign material on this fire Under no circumstances shall the...

Page 15: ...local Codes and or Regulations Ventilation fitted under or within immediate vicinity of the appliance must not be used as it may adverse ly effect performance of the combustion monitoring system ODS...

Page 16: ...ass cleaner Test on a small area first PAINTED AREAS These can be cleaned using a dry cloth STAINLESS STEEL AREAS These can either be cleaned using a proprietary stainless steel metal cleaner or baby...

Reviews: