DK50 3x4VR/M
NP-DK50-3x4VRM_ED-EN-2_10-2018
- 10 -
10/2018
Control calculation for dryer compressed air
dew point performance:
4
2
1
3
C
C
C
n
skut
C
F
F
F
Q
Q
F
Q
skut
= actual air flow
Q
n
= nominal flow through dryer (1800 l/min)
F
C1
= correction factor for working pressure
F
C2
= correction factor for temperature
entering into the dryer
F
C3
= dew point correction factor
F
C4
= ambient temperature correction factor
See the dryer user manual on the CD for more
details
7. PRODUCT DESCRIPTION
7.1.
Model variations and theiruses
The compressor is used as a central source of
clean, oil-free compressed air to power
individual devices and equipment with
compressed air used in large dental clinics
and laboratories, in hospital wards and other
settings where the parameters and properties
of the compressed air are suitable to the
specific application.
Compressed air supplied by the
compressor is unsuitable for use with
artificial lung ventilation devices without
further filtration.
Any use of the product outside its defined
uses as defined herein is considered misuse.
The manufacturer is not liable for any
damages or injury resulting from misuse.
7.2.
Deliveryincludes
DK50 3x4VR/M compressor
comprised of
(Fig.1):
-
compressor (air pumps with air tank)
-
dryer
module
(condensing)
with
connecting hoses
Fig. 1
Compressor
Compressor
Dryer module