The pressure sensor monitors the pressure in 
the  air  tank.  The  pressure  is  shown  on  the 
display. 

Check  all  air  line  connections  and 
check  for  compressed  air  leaks. 
Remedy all leaks that are identified.  

 
Slowly  open  the  outlet  valve  to  the  ON 
position.  The  compressor  starts  and  runs 
until the pressure in the entire compressed 
air  system  stabilises.  The  air  pumps  then 
gradually  turn  off  at  the  switching 
pressure. 
 
Complete  a  record  for  the  installation  of 
the 

compressor 

assembly 

and 

commissioning  (see  the  NP  -  Annex 
chapter – Page 44) 

 

SHUTTING DOWN THE COMPRESSOR 
 

Press the STOP button (18) to shut down the 
compressors. 
 

16.1.  Controller – operation and alarms 

The  controller  controls  the  air  pumps, 
monitors  their  operation,  analyses  faults, 
reports 

alarms 

and 

indicates 

when 

maintenance is required after defined intervals 
are met. 
 
The  controller  assesses  the  ambient  and 
internal  temperature  of  the  compressor, 
working pressure and operating hours.  
 
These  values,  alarms  and  service  interval 
information  are  shown  on  the  display. 
Temperatures  above  the  critical  values  are 
shown as alarms. 
 
The  control  panel  on  the  controller  has  four 
cursor  buttons  ▲,  ▼,  ►,  ◄,  ESC  and  OK 
buttons,  and  four  function  buttons  F1-F4, 
which trigger the following: 
 
 
 
 
 
 
 
 
 
 

 
 

F1

 - 

in alarm display mode, press  to switch 

back  to  normal  operating  mode  for  60 
seconds. Backlit screen. 
 

F2

 - 

information  on  operating  hours  and 

maintenance intervals 
 

F3

 - 

statistics  on  the  number  of  motor 

circuit  breaker  trips  from  motor  overcurrent 
above the defined motor circuit breaker limit 
 

F4 

SERVICE TECHNICIAN BUTTON  

(after completing service or maintenance work 
-  hold  for  5  seconds  to  reset  the  2,000  hour 
maintenance interval.) 

 

Note: Pressing F1-3 on the control panel turns 
on the display backlight for 30 seconds. 
 

16.1.1. Equipment operation 

Normal  operating  mode  is  shown  when  the 
equipment is operating and the functional and 
control  buttons  are  used  to  browse  through 
the following: 
 
Pressing

 F2 

:  

 
 
 
 
 
 
 
 
 
HOURS METER – air pump operating hours  
TIME–TO–GO 

MN 

time 

to 

next 

maintenance/service  
TOTAL    HOURS:    -  total  compressor 
operating hours  
NUMBER  of  MN  –  number  of  completed 
maintenance (service) checks confirmed using 
the F4 button 
 
The screen automatically returns to the home 
screen after 10 seconds. 
 
 Pressing

 F3 

:  

 
 
 
 
 
 

Summary of Contents for DK50 9x4VRT/M

Page 1: ...DK50 9x4VRT M User manual EN...

Page 2: ...October 2018 Z_2195 2018 Chap 3 pgs 5...

Page 3: ...RT M EKOM spol s r o Priemyseln 5031 18 SK 921 01 Pie any Slovak Republic tel 421 33 7967255 fax 421 33 7967223 www ekom sk email ekom ekom sk DATE OF LAST REVISION 10 2018 NP DK50 9x4VRTM_ED EN 2_10...

Page 4: ...EQUIPMENT FUNCTION 14 10 PNEUMATIC DIAGRAM 16 INSTALLATION 17 11 CONDITIONS FOR USE 17 12 PLACEMENT OF THE COMPRESSOR 18 13 PNEUMATIC CONNECTIONS 20 14 ELECTRICAL CONNECTIONS 21 OPERATION 25 15 INITIA...

Page 5: ...ther filtration Any use of the product outside the framework of its intended use is considered improper use The manufacturer is not liable for any damages or injury resulting from misuse 3 CONTRAINDIC...

Page 6: ...der authorized by the manufacturer the product is used pursuant to the user manual The user manual corresponds to the configuration of the product and its compliance with applicable safety and technic...

Page 7: ...ion occurs During repairs and maintenance ensure that product is disconnected from the mains pressure is released from all lines Only the manufacturer or a qualified specialist trained by the manufact...

Page 8: ...rking pressure bar 6 8 6 8 Safety valve bar 10 10 Noise level dB 85 74 Total weight of compressor net kg 747 817 Weight compressor module kg 540 610 Weight dryer module kg 80 80 Weight of air tank kg...

Page 9: ...pressor module kg 540 610 Weight dryer module kg 85 74 Weight of air tank kg 127 127 Compressor dimensions total w x d x h mm 3800x705 x2100 3800x705 x2100 Dimensions compressor module w x d x h mm 18...

Page 10: ...Correction factor for working pressure p bar 4 5 6 7 8 9 10 FC1 0 78 0 85 0 93 1 0 1 06 1 11 1 15 Correction factor for temperature of compressed air entering the dryer tinlet C 30 35 40 45 50 55 FC2...

Page 11: ...2 1 3 C C C n skut C F F F Q Q F Qskut actual airflow Qn nominal dryer flow 1800lit min FC1 working pressure correction factor FC2 correction factor for air entering the dryer FC3 dew point correction...

Page 12: ...ls a condensing dryer module with connection hoses air tank module DK50 9x4VRTS M compressor comprised of the following modules Fig 1b a compressor module with 9 compressor air pumps and controls alon...

Page 13: ...h a set of filters if needed A pressure regulator may be added to the set of filters The set of filters is fully compatible with all compressors listed above If a higher level of air filtration is req...

Page 14: ...ator and into the condensing dryer 9 This continues to lower the temperature of the air and produces more condensate The temperature then rises to reduce the relative humidity The clean dry air then p...

Page 15: ...0 9x4VRT M 10 2018 NP DK50 9x4VRTM_ED EN 2_10 2018 15 Fig 3 Electrical box switchboard 3 Electrical box switchboard 16 Display 17 Alarm indicator 18 Start stop button 19 Main switch 20 Temperature sen...

Page 16: ...VRTS M 1 Inlet filter 2 Compressor air pump 3 Compressor fan 4 Solenoid valve 5 Safety valve 6 Check valve 7 Pressure relief valve 8 Condensate separator 9 Dryer 10 Pressure sensor 11 Pressure gauge 1...

Page 17: ...e safety of the operator and maintenance personnel Operating the equipment in areas in which flammable mixtures may be present such as in operating rooms coal storage areas etc is prohibited Flammable...

Page 18: ...bly compressor dryer and air tank modules to remove all packaging and release the transport anchors from the pallet Anchors securing all modules to the pallet 12 1 Handling Use a fork lift truck or si...

Page 19: ...n Fig 7 Remove the transport stabilizers from the air pumps Fig 8 Remove all stabilizers on the air pumps once the compressor assembly has been positioned and levelled at the site of final installatio...

Page 20: ...2_10 2018 20 10 2018 Position the air tank at the site of installation and anchor it to the floor Fig 9 13 PNEUMATIC CONNECTIONS Compressor module dryer module connect the air tank with the provided h...

Page 21: ...valid technical standards The product is delivered without a power cord Connect the compressor module to the dryer module using the W22 cable Fig 14 Connect the compressor module to sensor B1 located...

Page 22: ...DK50 9x4VRT M NP DK50 9x4VRTM_ED EN 2_10 2018 22 10 2018 Fig 13 Fig 14 Fig 15 Cable bridge...

Page 23: ...addresses specific or requested from the manufacturer before the compressor is shipped or configure the IP addresses specific or requested based on the manual see the service manual or via the compres...

Page 24: ...ariables The second option for monitoring compressor parameters using selected memory variables is the LOGO Variable function Clicking on the LOGO Variable button shows the screen on the display that...

Page 25: ...witches on when pressure in the air tank drops to the pressure switch s lower limit level The compressor automatically switches off after reaching the pressure switch s upper limit level 15 INITIAL ST...

Page 26: ...hich the display returns to the start screen Note The START button is preset to RETENTIVITY ON which means that if the compressor has been activated once using the START button the system remembers th...

Page 27: ...nformation are shown on the display Temperatures above the critical values are shown as alarms The control panel on the controller has four cursor buttons ESC and OK buttons and four function buttons...

Page 28: ...y than maintenance service interval signals The maintenance service interval is measured from the first time the equipment is energised All alarms are accompanied by a blinking red P2 Alarm indicator...

Page 29: ...rmally Note The internal temperature monitoring function is not included for unenclosed compressors The display shows the current temperature inside the enclosed compressor module The alarm clears whe...

Page 30: ...N Data is recorded on a micro SD card in a slot in the base module See the illustration The figure shows the location of the micro SD card onto which alarms and operating events are logged Information...

Page 31: ...no risk of any other material damages Air pump components head cylinder and pressure hose are very hot when the compressor is running and just after it shuts down do not touch these components Repair...

Page 32: ...x x See the dryer manual on the CD user Check compressor fan operation x Visual check of rotation during air pump operation user Replace float in separator x x x 18 7 025200146 000 qualified professio...

Page 33: ...x x x 18 qualified professional Check temperature sensor switching function x x x x x x 18 12 qualified professional Replacement of piston group with bearing 6 8bar x x 604031764 000 qualified profes...

Page 34: ...r air pump for normal operation and noise levels Check the operation of fans Check the condition of filters Check the condition of the air pump itself contamination in the crankcase and play in the cr...

Page 35: ...er of turns until the valve itself vents Let the safety valve vent for only a few seconds Rotate the screw back to the right clockwise to the stop and the valve must be closed 18 7 Float replacement B...

Page 36: ...ers 3 Clean or wash the filter if heavily contaminated in a solution of soapy water and allow to dry completely Reinstall the filters once dry reverse the procedure to reassemble In Point A remove the...

Page 37: ...ank from 0 to 7 bar The measured value must be less than the data provided in the Technical data table 18 10 Check operation of check valves Compressed air circuit Check for proper operation of the ch...

Page 38: ...ator does not turn 18 12 Checking the operation of temperature sensor switching Fig 24 This check is conducted using the LOGO TDE display where the instantaneous temperature values are shown on the st...

Page 39: ...exceeds its pre set value The pressure relief valve closes as the pressure drops Pressure in the compressed air circuit can only increase because of an increase in flow resistance in the compressed a...

Page 40: ...tighten Check the main power connection replace if damaged Problem with electrical power source Main breaker is off Controller or expansion module malfunction Replace the malfunctioning controller or...

Page 41: ...or operation at a pressure of around 0 7 bar for a period of at least 1 hour then check the dryness of the compressed air 20 REPAIR SERVICE Guaranteed and post guarantee repairs must be done by the ma...

Page 42: ...DK50 9x4VRT M NP DK50 9x4VRTM_ED EN 2_10 2018 42 10 2018 ANNEX 22 MAPPING PARAMETERS...

Page 43: ...DK50 9x4VRT M 10 2018 NP DK50 9x4VRTM_ED EN 2_10 2018 43...

Page 44: ...lay panel alarms operation in alarm conditions Y N N C Installation connection to equipment Y C Product maintenance maintenance intervals maintenance procedure service intervals operating activities Y...

Page 45: ...TM_ED EN 2_10 2018 45 06 2018 DK50 9x4VRT M EKOM spol s r o Priemyseln 5031 18 921 01 PIE ANY Slovak Republic tel 421 33 7967255 fax 421 33 7967223 e mail ekom ekom sk www ekom sk NP DK50 9x4VRTM_ED E...

Reviews: