8
TECHNICAL DATA
Dimensions H x W x L:
685 x 460 x 480 mm
Weight:
48,5
kg
Electrical
connection:
1N~230V+PE
Fuse:
16A, slow
Rated
power:
3030W
Auxiliary
heating: 2000W
Air flow, free circulation:
800 m
3
/h
Refrigerant,
type: R134a
Carbon dioxide equivalents (CO
²
e): 500kg
Refrigerant, quantity:
350 g
Noise level (1 m in front):
67dB (A)
IP
rating: X4
Working range, temp:
+15–35°C
Working range, RH:
30-99%
Capacity: Max 1,3 l/h
(0,7 l/h at + 20°C 60% HD 1,3 l/h at + 30°C 80%HD)
* The product contains fluorescent greenhouse gases.
EU Declaration of Conformity see www.elbjorn.com
GB
INSTALLATION
POSITIONING
Position the dehumidifier horizontally on a wall console or floor frame.
Wall console and floor frame can be ordered as accessories. As an alternative, the
device can be placed on a floor console or another flat, stable surface close to a wall.
Adjust the feet so that the dehumidifier is horizontal.
WATER DRAINAGE
The drying room dehumidifier is fitted with an outlet for water drainage.
Fit a permanent condensation drain with a 15 mm compression joint or
alternately a ½" hose.
The drain pipe should be routed with a drop towards the floor drain.
If the drain pipe is very long, increase the size of pipe one step. The drainage
hole is located on the left side of the dehumidifier.
RESETTABLE FUSE
The socket on the left side of the machine is intended for control of the
associated fan.
The socket is protected by a 6 A resettable fuse that is located below the socket.
ELECTRICAL CONNECTION
Connect the CEE plug on the dehumidifier to a CEE socket,
1P+N+PE.
Fuse with at least a 16 A slow fuse.
See wiring diagram in the dehumidifier or
www.elbjorn.com.
WARNING!
Electrical connection of the wall outlet or additional
equipment for the drying room dehumidifier must be
performed by a qualified electrician according to national
installation regulations.