63
Local control (Logged in)
•
Select the desired language
•
In local control the minimum and maximum supply temperature must always be entered
•
Control: Set min. and max. supply temperature Recommended settings are 50–80°C. There must
always be at least five degrees between the min. and max. supply temperatures.
•
The circulation pump runs in auto mode between 45–100%
•
The supply temperature is kept between the set min. and max. temperatures
Changing circulation pump setting
•
Enter 55%. The pump operates between 55–100%
•
Enter 100%. The pump is fixed at 100%
•
The lowest setting for pump operation is 25%
Changing supply temperature setpoint
•
± raises or lowers the supply temperature control curve by the entered number of degrees
Zero MWh meter
•
Zeroes the energy consumption
Actuate servo
•
Operates the servo during servicing or maintenance.
Supply temperature control curve
GB
Outdoor temp.
Setpoint temp.
Extra temp.
-15
80
95 or max. temp. value
-10
74
89 or max. temp. value
-5
66
81 or max. temp. value
0
59
74 or max. temp. – normally 80 degrees
5
54
69
10
50
65