background image

IS--1379

February 2015

Page 4 of 4

OPERATING INSTRUCTIONS

Before Loadmake or Loadbreak Operation:

Ensure connector is clean and free of any contaminants. Ensure work area is clear of obstructions to allow installer to establish

firm footing and ensure a secure grasp on the hotstick tool. Maintain positive control over the movement of the loadbreak

connector before, during and directly after the operating sequence. Because of the control, speed and force required to

engage or disengage the elbow, certain operating positions are more advantageous than others. If there is some question as

to proper operating position, it is recommended that the connectors be operated de--energized. Do not connect two different

phases of a multiple--phase system. Before closing a single--phase loop, make certain both ends of the loop are the same

phase.

LOADMAKE OPERATION

Loadbreak connectors must be operated with a fully insulated ”hotstick” type live--line tool. Consult the

Utility’s safe work practices for the required live--line tool length.

1.

To prepare bushing for elbow connector, remove insulated cap by attaching hotstick tool to the insulated cap pulling

eye, and following the instructions for this accessory, remove from bushing.

2.

Securely fasten the hotstick to the loadbreak connector pulling eye.

3.

Confirm positive control of the elbow connector. Withdraw the elbow from the accessory device on the apparatus parking

stand with a fast, straight, firm motion being careful not to place the elbow connector near a ground plane.

Check appropriate accessory device operating instructions to be sure that the device is rated for energized operation.

4.

Insert the probe tip approximately 2” (50mm) into the bushing (at this point the contacts are approximately 4” apart).

DO NOT HOLD IN THIS POSITION BUT IMMEDIATELY PUSH THE ELBOW HOME WITH A FAST, FIRM, STRAIGHT

MOTION

.

Use sufficient force to engage the internal lock on the elbow connector and bushing interface.

Fault Close

1.

DO NOT CONDUCT LOADMAKE OPERATIONS ON KNOWN FAULTS

.

2.

If a fault is experienced, both the elbow connector and the bushing must be replaced.

LOADBREAK OPERATION

1.

Place desired accessory device on apparatus parking stand.

Refer to appropriate operating instructions for accessory device to be used. Confirm device is rated for energized operation.

2.

Firmly tighten the hotstick to the loadbreak connector pulling eye.

3.

Without exerting any pulling force, slightly rotate (clockwise) the connector in order to break surface friction prior

to disconnection.

4.

Withdraw the connector from the bushing with a fast, firm, straight motion, being careful not to place the connector near

a ground plane.

5.

Place connector on appropriate accessory device, following the operating instructions for that accessory.

VOLTAGE TEST

ELASTIMOLD

R

connectors equipped with an integral capacitance test point can be used to determine whether or not the

circuit is energized.

When using the test point, complete the following steps:

1.

Remove test point cap with the hotstick. When removing cap, PEEL OFF AT AN ANGLE rather than pulling directly in line

with the test point assembly.

2.

WARNING:

THE VOLTAGE TEST POINT IS A CAPACITANCE DEVICE, IT IS NOT DIRECTLY CONNECTED TO

THE CONDUCTOR. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the

meter that is used. Test with a suitable sensing device, made for use with separable connectors manufactured with

capacitive test points, to determine if cable is energized. Contamination, moisture, dirt, etc. around the test point or use

of the wrong measuring equipment can provide a false “no voltage” indication on an energized elbow. To prevent

serious or fatal injury treat the elbow as energized until the “no voltage” test point indication is confirmed by other means.

3.

After voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant supplied

and replace it on the test point.

THOMAS & BETTS CORP. PROPRIETARY AND CONFIDENTIAL

BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINED IN IT, AS WELL AS THE SUBJECT MATTER AND ALL PROPRIETARY AND NOVEL
FEATURES DISCLOSED, ARE OWNED BY THOMAS & BETTS CORP AND THAT DEVICES EMBODYING SUCH FEATURES OR INFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE
MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN CONSENT OF THOMAS & BETTS CORP. THESE DRAWINGS ARE NOT TO BE COPIED OR
REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN CONSENT OF THOMAS & BETTS CORP. ALL DRAWINGS AND INFORMATION ARE TO BE RETURNED TO UPON
DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT. COPYRIGHT THOMAS & BETTS CORP. ALL RIGHTS RESERVED. ALL OTHER TRADEMARKS ARE THE PROPERTY OF THEIR
RESPECTIVE OWNERS.

Summary of Contents for 161LRJS

Page 1: ... operated energized per operating instructions All deadbreak connectors must be de energized before operating Connectors must be operated with a full insulated hotstick type tool Consult the company s safe work practices for the required tool length FOR MORE INFORMATION ON PARTS INSTALLATION RATINGS AND COMPATIBILITY CALL THE NEAREST ELASTIMOLDR OFFICE Limited Warranty 1 T B warrants that its prod...

Page 2: ...ires imbedded into the first mastic strip Use the third strip of mastic if needed to build up the outer diameter in the area of the first mastic location Cover all mastic with vinyl tape D Remove insulation shield and insulation from the cable end Cut squarely taking care not to nick conductor E Wire brush bare aluminum conductors and immediately install compression lug Rotate to spread inhibitor ...

Page 3: ...RAL CONNECTION A Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and or rolling the seal down B Insert one end of a separate copper wire No 14 AWG 2 5mm or equivalent through the grounding eye on the elbow Twist tightly taking care not to damage the eye C Twist all neutral wires and connect to ground using appropriate connector Provide adequate slack in wires f...

Page 4: ...for energized operation 2 Firmly tighten the hotstick to the loadbreak connector pulling eye 3 Without exerting any pulling force slightly rotate clockwise the connector in order to break surface friction prior to disconnection 4 Withdraw the connector from the bushing with a fast firm straight motion being careful not to place the connector near a ground plane 5 Place connector on appropriate acc...

Reviews: