ELCO S.r.l. - ELK 38 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06261 - PAG. 10
5
SP3 Set Point 3
SPLL ÷ SPHL
0
6
SP4 Set Point 4
SPLL ÷ SPHL
0
7
SPLL
Low Set Point
-1999 ÷ SPHL
-1999
8
SPHL
High Set Point
SPLL ÷ 9999
9999
Group “InP” (parameters relative to the measure input)
Par.
Description
Range
Def.
Note
9 SEnS Probe type
input C :
J / CrAL / S /
Ir.J / Ir.CA /
Pt1 / 0.50 /
0.60 / 12.60
input E :
J / CrAL / S /
Ir.J / Ir.CA /
Ptc / ntc /
0.50 / 0.60 /
12.60
input I :
0.20 / 4.20
input V :
0.1 /
0.5 / 1.5 /
0.10 / 2.10
J
Ptc
4.20
0.10
10 SSC Low scale limit in case
of input with V / I
signals
-1999 ÷ FSC
0
11 FSC High scale limit in case
of input with V / I
signals
SSC ÷ 9999
0
12
dP Number of decimal
figures
Pt1 / Ptc / ntc:
0 / 1
norm sig.:
0 ÷ 3
0
13 Unit Temperature unit of
measurement
°C / °F
°C
14 FiL Input digital filter
0FF÷ 20.0
sec.
1.0
15 OFSt Measuring Offset
-1999 ÷ 9999
0
16 rot Rotation
of
the
measuring straight line
0.000 ÷ 2.000 1.000
17 InE “OPE” functioning in
case of measuring error
Our / Or / Ur
OUr
18 OPE Output power in case of
measuring error
-100 ÷ 100
%
0
Group “Out” (parameters relative to the outputs)
Par.
Description
Range
Def.
Note
19 O1F Functioning of output 1
1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
1.rEG
20 O2F Functioning of output 2 1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
ALno
Group “AL1” (parameters relative to alarm AL1)
Par.
Description
Range
Def.
Note
21 OAL1 Output where alarm
AL1 is addressed
Out1 / Out2 /
OFF
Out2
22 AL1t Alarm AL1 type
LoAb / HiAb
LHAb / LodE
HidE / LHdE
LoAb
23 Ab1 Alarm AL1 functioning
0 ÷ 15
0
24 AL1 Alarm AL1 threshold
AL1L÷ AL1H
0
25 AL1L Low
threshold
band
alarm AL1 or Minimum
set alarm AL1 for high
or low alarm
-1999 ÷ AL1H -1999
26 AL1H High threshold band
alarm AL1 or Maximum
set alarm AL1 for high
or low alarm
AL1L ÷ 9999
9999
27 HAL1 Alarm AL1 hysteresis
OFF ÷ 9999
1
28 AL1d Activation delay of
alarm AL1
OFF ÷ 9999
sec.
OFF
29 AL1i Alarm AL1 activation in
case of measuring error
no / yES
no
Group “LbA” (parameters relative to Loop Break Alarm)
Par.
Description
Range
Def.
Note
30 OLbA Output where alarm
LbA is addressed
Out1 / Out2 /
OFF
OFF
31 LbAt Time necessary to
activate alarm LbA
OFF ÷ 9999
sec.
OFF
Group “rEG” (parameters relative to the control)
Par.
Description
Range
Def.
Note
32 Cont Control type
Pid / On.FA
On.FS / nr
Pid
33 Func Functioning mode
output 1rEg
HEAt / CooL
HEAt
34 HSEt Hysteresis of ON/OFF
control
0 ÷ 9999
1
35 CPdt Compressor Protection
time for 2.rEG
OFF÷ 9999
sec.
0
36 Auto Autotuning Fast enable
OFF /
1 / 2 / 3 / 4
1
37 SELF Selftuning enable
no / yES
no
38
Pb
Proportional band
0 ÷ 9999
50
39
Int
Integral time
OFF ÷ 9999
sec.
200
40 dEr Derivative time
OFF÷ 9999
sec.
50
41 FuOc Fuzzy overshoot control 0.00 ÷ 2.00
0,5
42 tcr1 Cycle time of output
1rEg
0.1 ÷ 130.0
sec.
20,0
43 Prat Power ratio 2rEg / 1rEg 0.01 ÷ 99.99
1.00
44 tcr2 Cycle time of 2rEg
0.1 ÷ 130.0
sec.
10.0
45
rS
Manual reset
-100.0÷100.0
%
0.0
46 SLor Gradient of rise ramp
0.00 ÷ 99.99
/ InF
unit/min.
InF
47 dur.t Duration time
0.00 ÷ 99.59
/ InF
hrs.-min.
InF
48 SLoF Gradient of fall ramp
0.00 ÷ 99.99
/ InF
unit / min.
InF
49 St.P Soft-Start power
OFF /
-100 ÷ 100 %
OFF
50 SSt Soft-Start time
OFF /
0.1÷7.59
/ InF
hrs.-min.
OFF
Group “PAn” (parameters relative to the user interface)
Par.
Description
Range
Def.
Note
51 USrb Functioning of key “U”
noF / tunE /
OPLO / Aac /
ASi / CHSP /
OFF
noF
52 diSP Variable visualized on
the display
dEF / Pou /
SP.F / SP.o /
AL1
dEF
53 AdE Shift value for the shift
index functioning
OFF...9999
2
54 Edit Fast programming of
active Set Point and
alarms
SE / AE /
SAE / SAnE
SAE
5.2 - PARAMETERS DESCRIPTION
GROUP “
]
SP” (PARAMETERS RELATIVE TO THE SET POINT):
These allow the setting of the control Sets and the Sets
function modes.