background image

ELCO S.r.l. - ELK 38 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06261 - PAG. 11

 

nSP  –  NUMBER  OF  PROGRAMMABLE  SET  POINTS:  This  allows 
definition of the number of Set Points which will be programmed and 
stored (from 1 to 4). 
SPAt – ACTIVE SET POINT : If more than one Set Point is stored, 
this allows selection of the active Set Point.  
SP1 - SET POINT 1: Value of the Set Point n. 1  
SP2 - SET POINT 2: Value of the Set Point n. 2 (it appears if “nSP” 
>2 only) 
SP3 - SET POINT 3: Value of the Set Point n. 3 (it appears if “nSP” 
>3 only)  
SP4 - SET POINT 4: Value of the Set Point n. 4 (it appears if “nSP” 
=4 only)  
SPLL – LOW SET POINT: Lower value programmable as Set Point 
SPHL  –  HIGH  SET  POINT  :  Higher  value  programmable  as  Set 
Point 
 
GROUP  “ 

]

InP”  (PARAMETERS  RELATIVE  TO  THE  INPUTS): 

These  permit  the  definition  of  visualization  modes  of  the 
variable measured by the probe. 
SEnS
  –  PROBE  TYPE:  Depending  on  model,    it  permits  to  select 
the type of probe : 
-  thermocouples:  J  (J),  K  (CrAL),  S  (S)  or  ELCO  infrared  sensors 
IRS serie with J (Ir.J) or K (Ir.CA) linearization. 
- thermoresistances: Pt100 IEC (Pt1)  
- thermistors PTC KTY81-121 (Ptc) or NTC 103AT-2 (ntc) 
- normalized signals in current : 0..20 mA (0.20) or 4..20 mA (4.20) 
-  normalized  signals  in  tension:  0..50  mV  (0.50),  0..60  mV  (0.60), 
12..60  mV  (12.60),  0..1  V  (0.1),  0..5  V  (0.5),  1..5  V  (1.5),  0..10  V 
(0.10) or 2..10 V (2.10). 
SSC  –  LOW  SCALE  LIMIT  IN  EVENT  OF  INPUT  WITH  V/I 
SIGNALS    :  This  is  the  value  the  instrument  has  to  visualise  when  
the  minimum  value  that  can  be  measured  on  the  scale  (0/4  mA, 
0/12 mV, 0/1 V or 0/2 V) is present at the output. 
FSC  –  HIGH  SCALE  LIMIT  IN  EVENT  OF  INPUT  WITH  V/I 
SIGNALS    :  This  is  the  value  the  instrument  has  to  visualise  when 
the maximum value that can be measured on the scale (20 mA, 50 
mV, 60 mV, 1 V, 5 V or 10 V) is present at the input. 
dP  –  NUMBER  OF  DECIMAL  FIGURES:  It  permits  to  decide  if  the 
measuring resolution has to be 1 (0), 0.1 (1), 0.01 (2), 0.001 (3). In 
case  of  Pt100,  PTC  and  NTC  temperature  probes  the  allowed 
resolutions are 1° (0) and  0.1° (1). 
Unit  –  TEMPERTURE  UNIT  OF  MEASUREMENT  :  When  the 
temperature  is  measured  by  temperature  probes,  this  parameter 
permits  definition  if  the  visualisation  is  expressed  as  degree 
Centigrade (°C) or Fahrenheit (°F). 
Filt  –  INPUT  DIGITAL  FILTER  :  This  permits    programming  of  the 
constant of time of the software filter referring to the measured input 
value  (in  sec.)  in  order  to  reduce  noise  sensitivity  (increasing  the 
time of reading). 
OFSt – MEASURING OFFSET: Positive or negative Offset which is 
added to the value measured by the probe. 
rot  –  ROTATION  OF  THE  MEASURING  STRAIGHT  LINE:  In  this 
way  the  offset  programmed  on  par.  “OFSt”  is  not  constant  for  all 
measurements.  By  programming  “rot”=1.000,  the  value  “OFSt”  is 
simply added to the value read by the probe before visualisation and 
it  remains  constant  for  all  the  measurements.  If  instead  one  does 
not  want  the  programmed  offset  to  be  constant  for  all  the 
measurements, it is possible to carry out calibration on two desired 
values. 
 In this case, to define the values to be programmed on par. “OFSt” 
and “rot”, it is necessary to enforce the following formulae : 

“rot” = (D2-D1) / (M2-M1)  

“OFSt” = D2 - (“rot” x M2) 

where:  M1  =measured  value    1;  D1  =  visualisation  value  when  the 
instrument measures M1 
M2  =measured  value.  2;  D2  =  visualisation  value  when  the 
instrument measures M2 
It then follows that the instrument will visualise : DV = MV x “rot” + 
“OFSt” 
where:  DV = visualised value; MV= measured value 
InE  –  “OPE”  FUNCTIONING  IN  CASE  OF  MEASUREMENT 
ERROR:  This  defines  the  error  conditions  of  the  input  allowing  the 
instrument to give the power programmed on par. “OPE” as output. 
The possibilities are : 

= Or : the condition occurs in case of over-range or probe breakage 
=  Ur  :  the  condition  occurs  in  case  of  under-range  or  probe 
breakage 
= Our : the condition occurs in case of over-range or under-range or 
probe breakage 
OPE  –  OUTPUT  POWER  IN  CASE  OF  MEASUREMENT  ERROR: 
This permits setting of the power that the instrument has to give as 
output  in  case  of  measurement  error.    For  the  ON/OFF  regulators 
the power is calculated considering a cycle time equal to 20 sec. 
 
GROUP “ 

]

 Out” (PARAMETERS RELATIVE TO THE OUTPUTS): 

They permit to program the outputs functioning. 
O1F
  –  FUNCTIONING  OF  OUTPUT  OUT  1:  This  defines  the 
functioning  of  output  OUT  1  as:  control  output  1  (1.rEG),  control 
output  2  (2.rEG),  alarm  output  as  normally  open  (ALno),  output 
alarm normally closed (ALnc), output alarm normally closed with led 
reverse indication (ALni), output not used (OFF). 
O2F  -  FUNCTIONING  OF  OUTPUT  OUT  2:  Similar  to    “O1F”  but 
referring to output OUT2. 
 
GROUP  “ 

]

AL1” (PARAMETERS RELATIVE TO ALARM AL1): 

These permit setting of the process alarm AL1 function. 
OAL1
 – OUTPUT WHERE ALARM AL1 IS ADDRESSED: It defines 
to which output the alarm AL1 has to be addressed. 
AL1t  –  ALARM  AL1  TYPE:  permits  the  choice  of  behaviour  for 
alarm A1, by 6 different selections:   
=  LoAb  –  ABSOLUTE  LOW  ALARM  :  The  alarm  is  activated  when 
the process value goes below the alarm threshold set on parameter 
"AL1". 
=  HiAb  -  ABSOLUTE  HIGH  ALARM:  The  alarm  is  activated  when 
the process value goes above the alarm threshold set on parameter 
"AL1". 
=  LHAb  -  ABSOLUTE  BAND  ALARM:  The  alarm  is  activated  when 
the process value goes below the alarm threshold set on parameter 
"AL1L" or goes higher than alarm set on parameter "AL1H". 
=  LodE  –  DEVIATION  LOW  ALARM:  The  alarm  is  activated  when 
the process value goes below the value [SP + AL1] 
=  HidE  –  DEVIATION  HIGH  ALARM:  The  alarm  is  activated  when 
the process value goes above the value [SP + AL1] 
= LHdE – DEVIATION BAND ALARM: The alarm is activated when 
the process value goes below the value [SP + AL1L] or goes above 
the value [SP + AL1H] 
Ab1 – ALARM AL1 FUNCTION: This permits definition of alarm AL1 
functions,  by  entering  a  number  between  0  and  15.  The number to 
be  programmed,  that  corresponds  to  the  desired  function,  is 
obtained adding the values reported in the following description : 
ALARM BEHAVIOUR AT SWITCH ON: 
+0  =  NORMAL  BEHAVIOUR:  The  alarm  is  always  activated  when 
there are alarm conditions. 
+1  =  ALARM  NOT  ACTIVATED  AT  SWITCH  ON:  If,  at  switch  on, 
the instrument is in alarm condition, the alarm is not activated. It will 
be  activated  only  when  the  process  value  goes  beyond  and  then 
returns to alarm conditions. 
ALARM DELAY:  
+0  =  ALARM  NOT  DELAYED:  The  alarm  is  immediately  activated 
when the alarm condition occurs. 
+2  =  ALARM  DELAYED:  When  the  alarm  condition  occurs,  delay 
counting  starts  as  programmed  on  par.  “ALnd”  (expressed  in  sec.) 
and the alarm will be activated only after this time has elapsed. 
ALARM LATCH: :  
+  0  =  ALARM  NOT  LATCHED:  The  alarm  remains  active  in  alarm 
conditions only. 
+  4  =  ALARM  LATCHED:  The  alarm  is  active  in  alarm  conditions 
and remains active even if these conditions no longer exist, until the 
correctly programmed key “U” (“USrb”=Aac) has been pushed 
ALARM AKNOWLEDGEMENT: :  
+  0  =  ALARM  NOT  AKNOWLEDGED:  The  alarm  remains  always 
active in alarm conditions. 
+  8  =  ALARM  AKNOWLEDGED:  The  alarm  is  active  in  alarm 
conditions  and  can  be  deactivated  through  key  “U”  if  properly 
programmed (“USrb”=ASi), also if alarm conditions still exist. 
AL1 – ALARM AL1 THRESHOLD : Alarm AL1 threshold for low and 
high alarms. 

Summary of Contents for ELK 38

Page 1: ...ACTION PID CONTROL 4 6 DOUBLE ACTION PID CONTROL 4 7 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 9 SOFT STAR...

Page 2: ...er two seconds in the same condition the changing speed increases in order to allow the desired value to be reached rapidly Once the desired value has been reached by pushing key P it is possible to e...

Page 3: ...of the controller During automatic control it is possible to visualize the control power on the display by pushing key UP The range of the power values goes from H100 100 of the output power with rev...

Page 4: ...nearization J Ir J or K Ir CA for thermoresistances Pt100 IEC Pt1 or thermistors PTC KTY81 121 Ptc or NTC 103AT 2 ntc for normalised signals in current 0 20 mA 0 20 or 4 20 mA 4 20 for normalised sign...

Page 5: ...value SP HSEt Vice versa in case of direct action or cooling Func CooL it deactivates the output when the process value reaches SP HSEt in case of symmetrical hysteresis or SP in case of asymmetrical...

Page 6: ...control monitoring and the continuous calculation of the parameters during control Both functions automatically calculate the following parameters Pb Proportional Band tcr1 Cycle time of the output 1r...

Page 7: ...on only works through PID control and allows the limitation of control power when the instrument is switched on for a programmable period of time This is useful when the actuator driven by the instrum...

Page 8: ...ument is in alarm condition the alarm is not activated It will be activated only when the process value is in non alarm conditions and then back in alarm conditions ALARM DELAY the alarm output may be...

Page 9: ...CONFIGURATION BY KEY01 The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ELCO KEY01 with 5 poles conn...

Page 10: ...arm AL1L 9999 9999 27 HAL1 Alarm AL1 hysteresis OFF 9999 1 28 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 29 AL1i Alarm AL1 activation in case of measuring error no yES no Group LbA parameters...

Page 11: ...defines the error conditions of the input allowing the instrument to give the power programmed on par OPE as output The possibilities are Or the condition occurs in case of over range or probe breakag...

Page 12: ...with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 OFF Autotuning disabled When it s occurring an Autotuning cycle led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or...

Page 13: ...y to repeat the auto tuning LbA Loop control interrupted Loop break alarm Check the working of probe and actuator and swap the instrument to rEG control ErEP Possible anomaly of the EEPROM memory Push...

Page 14: ...C 58 0 230 0 F 0 20 mA SEnS 0 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 4 20 mA SEnS 4 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 0 50 mV SEnS 0 50 1999 9999 199 9 999 9 19 99 99 99 1 99...

Reviews: