ELCO S.r.l. - ELK 38 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06261 - PAG. 5

 

By using par. “InE” it is also possible to decide the conditions of the 
input  error,  allowing  the instrument to give the power  programmed 
on par. “OPE” as output. 
The possibilities of par. “InE” are : 
= Or : the condition occurs in case of over-range or probe breakage 
=  Ur  :  the  condition  occurs  in  case  of  under-range  or  probe 
breakage 
= Our : the condition occurs in case of over-range or under-range or 
probe breakage 
Using par. “diSP”, located in the group 

]

PAn”, it is possible to set 

normal  visualization  of  the  display  which  can  be  the  process 
variable (dEF), the control power (Pou), the active Set Point (SP.F) 
the Set Point operating when there are active ramps (SP.o) or alarm 
threshold AL1 (AL1). 
Again  in  the  group  

]

PAn”  the    par.  “AdE”  is  present  that  defines 

the 3 led shift index functioning. 
The lighting up of the green led = indicates that the process value is 
within  the  range    [SP+AdE  ...  SP-AdE],  the  lighting  up  of  the  led  – 
indicates  that  the  process  value  is  lower  than  [SP-AdE]  and  the 
lighting  up  of  the  led  +  indicates  that  the  process  value  is  higher 
than [SP+AdE]. 
 
4.2 - OUTPUTS CONFIGURATION 
The instrument’s outputs can be programmed by entering the group 
of  parameters  

]

Out,  where  the  relative  parameters    “O1F”  and 

“O2F”  (depending  on  the  number  of  outputs  available  on  the 
instrument) are located. 
The outputs can be set for the following functions : 
- Main control output (1.rEG) 
- Secondary control output (2.rEG) 
- Alarm output normally open (ALno) 
- Alarm output normally closed (ALnc) 
- Alarm output normally closed with led reverse indication (ALni) 
- Output deactivated (OFF) 
The  coupling  outputs  number  outputs  –  number  alarms  can  be 
made in the group referring to the alarm to the alarm (“

]

AL1”). 

 
4.3 – ON/OFF CONTROL (1rEG) 
All the parameters referring to the ON/OFF control are contained in 
the group 

]

rEG”. 

This  type  of  control  can be obtained by programming par."Cont" = 
On.FS or = On.FA  and works on the output programmed as 1.rEG, 
depending  on  the  measure,  on  the  active  Set  Point  “SP”,  on  the 
functioning mode "Func” and on the hysteresis "HSEt". 
The  instrument  carries  out  an  ON/OFF  control  with  symmetric 
hysteresis  if  “Cont"  =  On.FS  or  with  asymmetrical  hysteresis  if 
“Cont” = On.Fa. 
The  control  works  in  the  following  way  :  in  the  case  of  reverse 
action,  or  heating  (“FunC”=HEAt),  it  deactivates  the  output,  when 
the  process  value  reaches  [SP  +  HSEt]  in  case  of  symmetrical 
hysteresis,  or  [SP]  in  case  of  asymmetrical  hysteresis  and  is  then 
activated  again  when  the  process  value  goes  below  value  [SP  - 
HSEt].  
Vice  versa,  in  case  of  direct  action  or  cooling  ("Func”=CooL),  it 
deactivates the output, when the process value reaches [SP - HSEt] 
in  case  of  symmetrical  hysteresis,  or  [SP]  in  case  of  asymmetrical 
hysteresis    and  is  activated  again  when  the  process  value  goes 
above value [SP + HSEt]. 

 

 

4.4 - NEUTRAL ZONE ON/OFF CONTROL (1rEG - 2rEG) 
All  the  parameters  referring  to  Neutral  Zone  ON/OFF  control  are 
contained in the group 

]

rEG”. 

This  type  of  control  can  be  obtained  when  2  outputs  are 
programmed respectively as 1rEG and 2rEG and the par. “Cont” = 
nr . 
The  Neutral Zone control is used to control plants in which there is 
an element which causes a positive increase (ex. Heater, humidifier, 
etc.) and an element which causes a negative increase (ex. Cooler, 
de-humidifier, etc). 
The control functions works on the programmed outputs depending 
on  the  measurement,  on  the  active  Set  Point  “SP”  and  on  the 
hysteresis "HSEt". 
The  control  works  in  the  following  way  :  it  deactivates  the  outputs 
when  the  process  value  reaches  the  Set  Point  and  it  activates  the 
output 1rEG when the process value goes below value [SP - HSEt], 
or it activates the output 2rEG when the process value goes above 
[SP + HSEt].  
Consequently,  the  element  causing  a  positive  increase  has  to  be 
connected  to  the  output  programmed  as  1rEG  while  the  element 
causing  a  negative  increase  has  to  be  connected  to  the  output 
programmed as 2rEG. 

 

If  2rEG  output  is  used  to  control  compressor is possible to use the 
“Compressor  Protection”  function  that  has  the  meaning  to  avoid 
compressor “short cycles”. 
This function allows a control by time on the output 2rEG activation, 
independently by the temperature control request. 
The protection is a “delayed after deactivation” type. 
This  protection  permits  to  avoid  the  output  activation  for  a  time 
programmable  on  par.  “CPdt”  (expressed  in  sec.);  the  output 
activation will occurs only after the elapsing of time “CPdt”. 
The time programmed on parameter “CPdt” is counted starting from 
the last output deactivation. 
Obviously, whether during the time delay caused by the compressor 
protection  function,  the  regulator  request  should  stop,  the  output 
activation foreseen after time “CPdt” would be erased. 
The function is not active programming “CPdt” =OFF. 
The  led  relative  to  2rEG  output  blinks  during  the  phases  of  output 
activation delay, caused by “Compressor Protection” function. 
 
4.5 - SINGLE ACTION PID CONTROL (1rEG) 
All  the  parameters  referring  to  PID  control  are  contained  in  the 
group 

]

rEG”. 

The  Single  Action  PID  control  can  be  obtained  by  programming 
par."Cont" = Pid  and works on the output 1rEG depending on the 
active Set Point “SP”, on the functioning mode "Func” and on the 
instrument’s PID algorithm with two degree of freedom. 

 

Summary of Contents for ELK 38

Page 1: ...ACTION PID CONTROL 4 6 DOUBLE ACTION PID CONTROL 4 7 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 9 SOFT STAR...

Page 2: ...er two seconds in the same condition the changing speed increases in order to allow the desired value to be reached rapidly Once the desired value has been reached by pushing key P it is possible to e...

Page 3: ...of the controller During automatic control it is possible to visualize the control power on the display by pushing key UP The range of the power values goes from H100 100 of the output power with rev...

Page 4: ...nearization J Ir J or K Ir CA for thermoresistances Pt100 IEC Pt1 or thermistors PTC KTY81 121 Ptc or NTC 103AT 2 ntc for normalised signals in current 0 20 mA 0 20 or 4 20 mA 4 20 for normalised sign...

Page 5: ...value SP HSEt Vice versa in case of direct action or cooling Func CooL it deactivates the output when the process value reaches SP HSEt in case of symmetrical hysteresis or SP in case of asymmetrical...

Page 6: ...control monitoring and the continuous calculation of the parameters during control Both functions automatically calculate the following parameters Pb Proportional Band tcr1 Cycle time of the output 1r...

Page 7: ...on only works through PID control and allows the limitation of control power when the instrument is switched on for a programmable period of time This is useful when the actuator driven by the instrum...

Page 8: ...ument is in alarm condition the alarm is not activated It will be activated only when the process value is in non alarm conditions and then back in alarm conditions ALARM DELAY the alarm output may be...

Page 9: ...CONFIGURATION BY KEY01 The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ELCO KEY01 with 5 poles conn...

Page 10: ...arm AL1L 9999 9999 27 HAL1 Alarm AL1 hysteresis OFF 9999 1 28 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 29 AL1i Alarm AL1 activation in case of measuring error no yES no Group LbA parameters...

Page 11: ...defines the error conditions of the input allowing the instrument to give the power programmed on par OPE as output The possibilities are Or the condition occurs in case of over range or probe breakag...

Page 12: ...with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 OFF Autotuning disabled When it s occurring an Autotuning cycle led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or...

Page 13: ...y to repeat the auto tuning LbA Loop control interrupted Loop break alarm Check the working of probe and actuator and swap the instrument to rEG control ErEP Possible anomaly of the EEPROM memory Push...

Page 14: ...C 58 0 230 0 F 0 20 mA SEnS 0 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 4 20 mA SEnS 4 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 0 50 mV SEnS 0 50 1999 9999 199 9 999 9 19 99 99 99 1 99...