MENU OF INSTRUMENT PROGRAMMING (

SETUP

)

 

After the connecting the power supply to the instrument and waiting few seconds (all LED’s will glow and the first 
indication of the firmware appears on the display and all segments will glow later), press and keep pressing the key 

during 5 seconds, when the message seT  UP  will appear on the display 

E

The values set are hold also in absence of the auxiliary power supply. 

 

SET GENERAL PARAMETER (

SET   UP

)

 

Entry to menu: 

seT  UP  

Æ

  

seT  Up 

RESET 
SET   DO1 
SET   DO2 
SET   HR_ 

ELM-96 

instruction manual

IM425-U v3.1 

pag. 7

 

DO_   OFF   OFF 

 

SET   CT                                                 

Increase

 

Set CT ratio

 

from 1 to 2000                           

Decrease

 

 

SET   VT                                                 

Increase

 

Set VT ratio

 

from 0.1  to 400.0                       

Decrease

 

 

seT AV9 T                                         

Increase

 

Set average time

 

from 1 to 30 minutes                             

Decrease

 

 

seT 3pH                                   BALANC 

Set connection                                     

UN_BAL 

Type                                                       

1PH   L3 

 

seT  MDE                                              -3- 

Set wiring connection

 

type                                                        

-4- 

 

seT SYN MDE                                    L3 

Set synchronism                                  

50 

type                                                        

60 

 

seT  SCHROLL 

ON 

OFF 

 

SET   PAS                                              

Increase

 

Set Password

 

OFF   - 0002 ÷ 9999                 

Decrease

 

 

Confirm and end of general settings

 

 

- Programming of the transformation rate of the external CT’s

 

The programming of the CT’s rate considered as the rate between primary and secondary (example: with CT 1000/5, we 
must set 200), must be done with the push-button on the front panel. 
By pressing the key 

again it will appear the message CT (current transformer) and the value of the transformation rate 

(set to 1 by the manufacturer). To increase the value press the 

button while to reduce the value press the 

button with 

already pressed (the variation is unit for unit). To increase the speed up the value setting, it’s necessary to hold 

pressed the 

or the couple 

and 

buttons, the variation will happen successively by tens and hundreds. To come back 

to increase or to reduce the value on unit by unit way, it’s necessary to release and to press the key again. To confirm the 
value set press the 

button; in this way the instrument will pass to the successive programming. 

If no key is pressed during a 10-second interval of time, the instrument will exit automatically from programming, without 
saving the selected value. 

Summary of Contents for ELM-96

Page 1: ...DELS ELM 96 ACCESSORI ED OPZIONI accessories transparent cover for frontal protection options C1 auxiliary power supply 230 V C2 auxiliary power supply 115 V 1A current inputs for CT 1Amp T current in...

Page 2: ...se to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phas...

Page 3: ...ith 3 wires without neutral or with neutral not supplied the N terminal must not be connected ELM 96 instruction manual IM425 U v3 1 pag 3 P1 L1 S1 L2 S1 L3 P1 N S1 S2 P1 P2 LOAD ELM INSERTION ON THRE...

Page 4: ...ERTION ON THREE PHASE LINE WITH 2 CT insertion AARON L1 S1 P1 L2 L3 N S1 S2 P1 P2 LOAD ELM VOLTAGE INSERTION ON THREE PHASE LINE WITH 3 WIRES WITH 2 VT This insertion is possible only with the interna...

Page 5: ...3 wires without neutral or with neutral not supplied the N terminal must not be connected ELM 96 instruction manual IM425 U v3 1 pag 5 L1 L2 L3 S1 S2 P1 P2 LOAD ELM INSERTION ON SINGLE PHASE LINE Only...

Page 6: ...lise on display E C LED s for indicating the measures visualised on display E and the eventual multiplier factor of each parameter reading k kilo x1000 D LED for indicating the visualisation of the me...

Page 7: ...Decrease Confirm and end of general settings Programming of the transformation rate of the external CT s The programming of the CT s rate considered as the rate between primary and secondary example w...

Page 8: ...With the 4 wires connection the neutral parameter are displayed and enabled to use for the digital outputs settings Programming of the synchronism type In this setting for the synchronization type it...

Page 9: ...e ALR Dl Decrease ENTER IN THE SETUP Confirm and end of digital output settings Fromthemeasuresvisualization presstheAkeyforatleast5seconds themessageSeT Up willappearontheEdisplays CHOOSE THE DIGITAL...

Page 10: ...delay Functioning for exceeding the maximum threshold With only the LO threshold set the alarm condition is activated when the parameter set in alarm drop below the threshold The digital output is ena...

Page 11: ...s SELECT THE PARAMETER TO LINK TO THE HOURS COUNTER From the previous setting pressing the B key it s possible to set the hours counter the message SET HR_ appears on the E display Press the A key to...

Page 12: ...urrent LED Hz ON on L3 display is showed the frequency measured on L3 phase on L1 display will appear the message PHASE ROTATION with a bright dash that rotate clockwise to indicate that the phase rot...

Page 13: ...LED L on VL N k VL L k A k VL N VL L In balanced three phase system mode BALANC are available only the visualization 7 and 8 In single phase mode PH L3 the pages displayed are the following ELM 96 ins...

Page 14: ...key are as follows Parameter Display Signalling LED VL N maximum instantaneous PEA HI VL N VL N minimum instantaneous Pea LO VL N VL L maximum instantaneous PEA HI VL L I phase maximum instantaneous P...

Page 15: ...oad 20 impedance at the input 1 M Three phase wiring with 3 or 4 wires and single phase wiring MV connection through external VT with programmable transformation ratio from 1 to 400 Current inputs Fro...

Page 16: ...panel 96 96 90 92 ELM 96 R3 avg 92 20 For other applications please contact with ELCO technical assistance department Via Lago di Molveno 20 36015 Schio VI Tel 39 0445 661722 Fax 39 0445 661792 http...

Reviews: