background image

ELM-961 

 

instruction manual

IM441-U v0.6 

pag. 10

 

ENTER IN THE SETUP 
From the measures visualization, press at the same time the A and C keys, the message Set  Up  will appear on the F 
displays. 
CHOOSE THE DIGITAL OUTPUT TO PROGRAM 
Press repeatedly the C key until the message SET   DO1  (DO1 output) or SET   DO2  (DO2 output) appears on the F 
display. Press the A key to select this setting. 
SELECT THE MODALITY OF FUNCTIONING OF THE DIGITAL OUTPUT 
To select the functioning mode, using the B and C keys, it’s possible to select: PULSE  (pulse emission), ALR   SYS 
3PH, (alarm on three phase value), ALR   PH_ 123 (alarm on minimum and maximum single phase value) and BY_ 
REMOTE  (the digital output is managed using serial output). Press A key to confirm. 
CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT 
With an alarm modality set, it’s necessary to select the parameters associated to the alarm output; by pressing the B and 
C keys until the parameter choice appears on the third part (L3) of F display and the glowing the corresponding led on the 
D bar. Press A key to confirm the set. 
SET THE HIGH AND THE LOW THRESHOLDS 
On F display will appear the message  ALR   Hi  with  the high threshold value; confirming with the A key on the same 
display will appear the message ALR   LO  with low threshold value. The B (to increase) and C (to decrease) keys are 
used to set the high and the low thresholds values. The range depends by the parameter and it is linked to the CT and VT 
ratios. Pressing A key to confirm. 
The threshold set is linked with CT and VT ratios, for this reason it’s necessary to make this operation after the 
programming of the CT and VT. The end scale value must be confirmed when CT and VT ratios are modified. 
The low threshold will be lower than high threshold. If the high threshold is set as OFF the low threshold will have the 
range of the high threshold. 
SET THE DELAY TO THE DIGITAL OUTPUT ACTIVATION 
Now it’s possible to set the delay that will pass between the alarm condition set and the activation of digital output. On F 
display will appear ALR   DLY  and the value expressed in seconds (range 1÷900). The modification of the value is done 
in the same way of the threshold set. With the confirmation (A key) the set is complete. 
The programming will be referred to the digital output indicated on G display (DO1  o DO2). 

Summary of Contents for ELM-961

Page 1: ...internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS paramete...

Page 2: ...400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V...

Page 3: ...IRES ELM on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 S1 P1 S1 L2 P1 L3 N S1 S2 P1 P2 LOAD I1 I3 VL1 VL2 VL3 INSERTION ON THREE PHASE LINE...

Page 4: ...N ON SINGLE PHASE LINE I1 I2 S1 I3 VL1 VL2 VL3 if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase sys...

Page 5: ...the values of the active reactive and apparent energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electr...

Page 6: ...kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR In...

Page 7: ...decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization...

Page 8: ...rd when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page o...

Page 9: ...ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of t...

Page 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Page 11: ...ime the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I...

Page 12: ...all the measures appear on the L3 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltag...

Page 13: ...s max maxD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg W max avg VAr max avg VA max avg three phase power maximum of average thr...

Page 14: ...se speed Not shielded connection As shown in the diagram it is necessary to place a serial RS232 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termin...

Page 15: ...ELM 961 instruction manual IM441 U v0 6 pag 15 DIMENSIONS ELM 961 96 9 56 cut panel 96 96 R3 92 90 92 20...

Page 16: ...1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outpu...

Reviews: