Programming of the baud rate (SET BDR) (only for vers. with serial output)
The following setting is the baud rate. The message SET appears on G display, the message SET BDR on the first two
parts of F display to indicate the programming of the baud rate displayed on the third part (L3) of the F display. To modify
the value set, it’s necessary to use the C key to decrease and B to increase the rate. The values settable are:
- 19.2 => 19200 baud
- 9.60 => 9600 baud
- 4.80 => 4800 baud
- 2.40 => 2400 baud
Press A to confirm the value displayed.
Programming of the serial parameters (only for vers. with serial output)
ELM-961
instruction manual
IM441-U v0.6
pag. 8
8 1
8 data bit / 1 stop bit
PAR
No parity
NO
8 2
8 data bit / 2 stop bit
PAR
No parity
NO
8 1
8 data bit / 1 stop bit
PAR
Even parity
EVE
8 1
8 data bit / 1 stop bit
PAR
Odd parity
ODD
On G display will appear the message SET. The following message will appear on F display using the B and C keys. To
confirm press the A key.
Programming of the Password (SET PAS)
The instrument is supplied without password. When a password (from 0002 to 9999) is set, using the B (to increase), C
(to decrease) and A (to confirm) keys, only who know this value can to enter in the setup. The password, in fact, is
required all the time that someone try to enter in the setup (pressing the A and B key at the same time). If the password
is wrong, the message PASS ERR will appear on F display and the instrument go back to the measures visualization.
To input the password, when required by the instrument, at the enter of the setup, use the A, B and C keys as the same
way done previously.
The menu is cyclic. After the last setting, the instrument go back to the first page of Setup (SETUP). It’s always possible
to come back to measures visualization mode pressing at the same time the A and C keys.
PEAK VALUES AND ENERGY COUNTERS RESET (RESET)
From the measures visualization mode, pressing the A and C keys simultaneously the message SETUP will appear on F
display, press the key C until the message RESET appears on the same display. To accede to the menu, press the A
key. Now it’s possible to select the enabling of cancellation type, by pressing the C key, according with following types:
RESET PEA: all maximum value will be delete.
RESET AVG: all average and average maximum value (maximum demand) will be delete.
RESET EN: with NORMAL as energy mode (EN) the total energy counters will be delete, with TOT PAR the partial
energy counters will be delete.
RESET ALL: to delete all average and maximum values and all energy hours counters.
Entry to menu:
seT UP
Æ
seT Up
RESET
SET DO1
SET DO2
SET HR_
--- OFF OFF
(the visualization depends on the settings and the I/O status)
RESET PEA
NO / YES
Confirm Reset
Deleting maximum values (max)
RESET AVG
NO / YES
Confirm Reset
Deleting average values (avg)
and maximum demand (maxD)
RESET EN
NO / YES
Confirm Reset
Deleting energy counters
RESET ALL NO
/
YES
Confirm
Reset
Deleting maximum and average
values, and energy counters
To enable the chosen type, press the B key to change the indication on display G from NO to yes.
Confirm enabling cancellation, by pressing the A key. The indication on display G change from yes to --- .