PROGRAMMING OF THE DIGITAL  OUTPUT (SET   DO1         SET   DO2)  (only  for  vers.  with  digital  output) 
The DO1 and DO2 digital outputs have three modality of functioning: PULSE, alarm (ALR)  and REMOTE  command. 
The DO1 modality setting is independent from DO2. For example it’s possible to set DO1 on PULSE (pulse emission) 
and DO2 on alarm mode (ALR). 

 

In the menu SET   DO1  and SET   DO2  it’s possible to program the function of all digital outputs. In these menus are 
available the following modality: PULSE, ALR  and REMOTE. 
In PULSE mode the digital output DO1 will emit pulses proportional to the active energy counted while the digital output 
DO2 will emit pulses proportional to the reactive energy counted. The proportionality will depend from the PULSE set in 
the SETUP and the duration of the impulse is set in the TPL  voice of the SETUP. 
The ALR  modality is divided in two parts: ALR   SYS   3PH and ALR   SYS   123. With ALR   SYS   3PH the digital 
output will function as alarm verifying that the three phase value doesn’t exceed the threshold set (ALR   HI  and ALR 
LO).  With ALR   SYS   123 the digital output will function as alarm verifying that the maximum value of the single phases 
doesn’t exceed the maximum threshold set (ALR   HI)  and that the minimum value of the single phases doesn’t come 
down the minimum threshold set (ALR   LO).  The activation of the alarm output will come after some seconds of delay 
set(ALR   DL). 
In the REMOTE  mode, the output status will be decided from the status of the correspondent MODBUS register (see 
protocol modbus manual for ELM). 
Enter to menu: 

ELM-961 

 

instruction manual

IM441-U v0.6 

pag. 9

 

seT  UP  

Æ  

seT  Up 

RESET 
SET   DO1 
SET   DO2 
SET   HR_ 
--- OFF   OFF  

(the visualization depends on the settings and the I/O status) 

 

PUl se  To 

choose 

the 

output 

 

modality 

ALR   SYS   3PH  (selecting 

PULSE or 

ALR   PH_ 123  

BY_ REMOTE 

BY_  REMOTE  

the setting finish) 

 

ALR   SEl uLN 
ALR   SEl AMP 
ALR   SEl P.f  To 

chose 

the 

parameter 

ALR   SEl ACT  

to  control 

ALR   SEl REA  

(see variable list) 

ALR   SEl APP 
ALR   SEl VLL 
ALR   SEL   FRE  (only for ALR   SYS   3PH) 
AlR sel  T°c (only for ALR   SYS   3PH) 

 

Set maximum  alarm threshold  

Increase 

 

ALR   HI  

Decrease  (after  0 there is OFF) 

Set minimum alarm  threshold  

Increase 

ALR   LO  

Decrease  (after  0 there is OFF) 

Set delay  

Increase 

ALR   Dl  

Decrease 

 

Confirm  and end of digital  output  settings. 

Summary of Contents for ELM-961

Page 1: ...internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS paramete...

Page 2: ...400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V...

Page 3: ...IRES ELM on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 S1 P1 S1 L2 P1 L3 N S1 S2 P1 P2 LOAD I1 I3 VL1 VL2 VL3 INSERTION ON THREE PHASE LINE...

Page 4: ...N ON SINGLE PHASE LINE I1 I2 S1 I3 VL1 VL2 VL3 if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase sys...

Page 5: ...the values of the active reactive and apparent energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electr...

Page 6: ...kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR In...

Page 7: ...decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization...

Page 8: ...rd when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page o...

Page 9: ...ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of t...

Page 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Page 11: ...ime the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I...

Page 12: ...all the measures appear on the L3 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltag...

Page 13: ...s max maxD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg W max avg VAr max avg VA max avg three phase power maximum of average thr...

Page 14: ...se speed Not shielded connection As shown in the diagram it is necessary to place a serial RS232 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termin...

Page 15: ...ELM 961 instruction manual IM441 U v0 6 pag 15 DIMENSIONS ELM 961 96 9 56 cut panel 96 96 R3 92 90 92 20...

Page 16: ...1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outpu...

Reviews: