background image

 

ELM-96BP-LON

 

instruction manual 

IM447-U v0.67 

pag. 11  

MEASURES VISUALIZATION 

The instrument is divided in two distinct section: 
the first is composed by three displays (

F

), by 

A

 and 

B

 keys and by 

LED bar 

D

; the second (in the low part) is composed by 

G

 display, 

by 

C

 key and by LED bar 

E

The two sections are to consider as two different instruments in a 
only one box, in fact it’s possible to act in a zone without to modify 
the visualization in the other (peak value and energy counters 
visualization excluded). 
 

Visualization section 1 

The three measures of phases (on L1, L2 and L3), of the parameter 
indicated from the led 

D

 on, appears on 

F

 display. For the measure of the phase to phase voltages (V 

L-L

), the three 

measures are V 

L1-L2

, V 

L2-L3

, V 

L3-L1

It’s necessary to press the 

B

 button to select the parameter that can be displayed and indicated from 

D

 LED. 

Press 

A

 button to see on 

F

 display the three phase value (the average of the single phase of voltage, current, power 

factor and the sum of single phase for the power) of the parameter selected,: the led inside the 

A

 key is on. 

To press another time the same key the visualization come back at the phase values. 
The unit of measurement can be expressed in kilo or Mega, in the this case the relative LED is on. 
A sign – on the first digit indicates the visualization of the capacitive power factor (example the reading 

-.95

 indicates 

a power factor of 

0.95

 capacitive) 

Note: If in the Setup the single phase mode (

1PH L1

) is set, all the measures appear on the L1 display. 

 

Visualization section 2 

At the same way of the section 1, press the 

C

 button to select the parameter that can be displayed and indicated from 

E

 LED. The voltage values are of the three phase system, the frequency is of the L1 channel. 

 

Visualization energy and hours counters 

With the 

C

 key it’s possible to visualize on 

F

 display the active, reactive and apparent energy counters. One segment 

of the right digit of the 

G

 display, in correspondence of the 

kWh

 and 

KVArh

 on the front panel, turn on, to indicate the 

visualization of the active and reactive energy counters. The led 

VA

 and the segment of the right digit of the 

G

 display, 

in correspondence of 

…h

 on the front panel, turn on, to indicate the visualization of the apparent energy counter. To 

complete the visualization the led 

k

 over the 

F

 display could be on. 

This is the visualization if 

NORMAL

 is the set in 

EN

 voice of the setup. Instead if the setting is 

TOT PAR

 on the 

F

 

display will be visualized alternatively the partial and the total active, reactive and apparent energy counters; the first 
digit of the 

G

 display indicates the type of the counter: 

P

 for the partial (the user could be reset it) and 

T

 for the total 

(it’s no possible to reset it). 
 
The right digit of 

G

 display, in correspondence of the 

…h

, turn on, when the visualization of hours counters is active. 

The reading of the counters use the 9 digits (maximum reading 99999999.9) of the 

F

 display: the measure is 

displayed in the way that the L1 display will indicate the first 3 digits, the display L2 the seconds 3 digits and the L3 
display the last 3. 
For example if: L1=000, L2=028, L3=53.2 the reading is 2853.2 kWh. 

Summary of Contents for ELM-96BP-LON

Page 1: ...65 options insulated current inputs neutral current input or residual current input MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N Σ V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 Σ V L L phase and three phase currents A kA A L1 A L2 A L3 Σ A neutral current A kA An phase and thre...

Page 2: ...s not suffered any damage during transport When starting installation make sure that the operating voltage and mains voltage are compatible with the device instructions The instrument power supply must not be earthed Maintenance and or repair must be carried out only by qualified and authorized personnel If there is ever the suspicious that that there is a lack of safety during operation the instr...

Page 3: ...rmers with secondary 5A it s possible to use 2 TA on lines with 3 wires insertion three phase Aron The utilization of external TA is obligatory With the neutral current input option installed the multimeter allows the measure of the neutral current using a current transformer 5A the secondary must be connected to the In S1 and S2 terminals available on the rear of the instrument see the wiring dia...

Page 4: ...WIRING DIAGRAMS ELM 96BP LON instruction manual IM447 U v0 67 pag 4 ELM 96BP LON instruction manual IM447 U v0 67 pag 4 ...

Page 5: ...ree phase system value of the electrical measure selected LED k and M show the eventual multiplying factor k kilo x 1 000 M Mega x 1 000 000 Using the C key the display indicates also the values of the active and reactive energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy co...

Page 6: ...T Increase Set CT ratio from 1 to 2000 Decrease SET VT Increase Set VT ratio from 0 1 to 400 0 Decrease version with An input SET CTN Increase Set CT ratio of the neutral input from 1 a 2000 Decrease seT AV9 T Increase Set average time from 1 to 30 minutes Decrease seT EN TOT PAR Set Energy visualization type NORMAL seT 3pH BALANC Set connection UN_BAL type 1PH L1 seT MDE 3 Set wiring connection t...

Page 7: ...ssage CTN Current transformer neutral ratio and the set value on the F display In the same way at the programming of the CT rate will be possible to set this value example with CT 1000 5the value will be 200 Pressing the A key confirm and go away with the next setting Programming of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F...

Page 8: ...s and the I O status RESET PEA NO YES Confirm Reset Deleting maximum values max RESET AVG NO YES Confirm Reset Deleting average values avg and maximum demand maxD RESET EN NO YES Confirm Reset Deleting energy counters RESET ALL NO YES Confirm Reset Deleting maximum and average values and energy counters To enable the chosen type press the B key to change the indication on display G from NO to yes ...

Page 9: ...serial output Press A key to confirm CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT With an alarm modality set it s necessary to select the parameters associated to the alarm output by pressing the B and C keys until the parameter choice appears on the third part L3 of F display and the glowing the corresponding led on the D bar Press A key to confirm the set SET THE HIGH AND THE LOW THRESHOLD...

Page 10: ...ime the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the first part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the...

Page 11: ...l the measures appear on the L1 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent e...

Page 12: ...imum three phase powers Σ max maxD avg I L1 max avg I L2 max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg Σ W max avg Σ VAr max avg Σ VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg I N avg phase and neutral currents average phase and neutral cu...

Page 13: ...20 60Vac 24 72Vdc Version Vac dc 80 230Vac 90 250Vdc consumption max 4VA voltage inputs from 20 to 500V phase phase permanent overload 20 input impedance 1 MΩ insertion on three phase line with 3 wires 4 wires and single phase insertion in MT with external TV and transforming rate programmable from 1 to 400 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A pri...

Page 14: ...12 nvo_3ph_cos nvo_3ph_pwr nvo_3ph_AVAh_T1 nvo_voltage_l23 nvo_cos_ph1 nvo_pwr_ph1 nvo_3ph_AVAh_T2 nvo_voltage_l31 nvo_cos_ph2 nvo_pwr_ph2 nvo_cos_ph3 nvo_pwr_ph3 nvo_3ph_Rpwr nvo_Rpwr_ph1 nvo_Rpwr_ph2 nvo_Rpwr_ph3 nvo_MaxAvg3PhAP nvo_MaxAvg3PhRP nvo_MaxAvg3PhApP nvo_LastAv3PhAcP nvo_LastAv3PhRP nvo_LastAv3PhApP SNVT_switch SNVT_freq_hz SNVT_amp_mil SNVT_temp SNVT_count SNVT_state nvo_Debug nvo_Fr...

Page 15: ...mp_mil nvo_MaxAvgCurrL3 MAX AVG CURRENT L3 A SNVT_power_f nvo_MaxAvg3PhAP MAX AVG 3 PH ACTIVE POWER kW SNVT_power_f nvo_MaxAvg3PhRP MAX AVG 3 PH REACTIVE POWER kVAr SNVT_power_f nvo_MaxAvg3PhApP MAX AVG 3 PH APPARENT POWER kVA SNVT_power_f nvo_LastAv3PhAcP LAST AVERAGE 3 PHASE ACTIVE POWER kW SNVT_power_f nvo_LastAv3PhRP LAST AVERAGE 3 PHASE REACTIVE POWER kVAr SNVT_power_f nvo_LastAv3PhApP LAST A...

Page 16: ...Via Lago di Molveno 20 36015 Schio VI Tel 39 0445 661722 Fax 39 0445 661792 http www elco italy com E mail info elco italy com support elco italy com ELM 96BP LON instruction manual IM447 U v0 67 pag 16 ...

Reviews: