Technical data
Technical data Trigon XXL EVO 1700 (pre-liminary)
6
1200
1400
1550
1700
Nominal heat output at 80-60ºC max/min
kW
1629/466
Nominal heat output at 40/30ºC max/min
kW
1714/490
Nominal heat input Hi max/min*
kW
1666/476
Efficiency at 80/60ºC
%
97.8
Efficiency at 40/30ºC
%
102.9
Standstill losses (T
water
= 70ºC)
%
0,2
Max. condensate flow
l/h
-
Gas consumption H-gas max/min (10,9 kWh/m
3
)
m
3
/h
153.9/42.0
Gas consumption L-gas max/min (8,34 kWh/m
3
)
m
3
/h
201.1/54.9
Gas consumption LPG. max/min (12,8 kWh/kg)
kg/h
Gas pressure H-gas
mbar
50
Gas pressure L/LL-gas
mbar
50
Gas pressure LPG
mbar
50
Maximum gas pressure
mbar
100
Flue gas temperature at 80/60ºC max/min
ºC
81.2/61.2
Flue gas quantity max/min*
m
3
/h
3631/908
CO
2
level main burner natural gas H/E/L/LL max/min
%
10.0/9.3
CO
2
level main burner liguid gas P max/min
%
11.0/11.0
CO
2
level pilot burner natural gas H/E/L/LL max/min
%
10.0/10.2
CO
2
level pilot burner liguid gas P max/min
%
11.0/11.2
NOx level max/min
mg/kWh
61.4/22.0
CO level max/min
mg/kWh
9.8/3.3
Max. permissible flue resistance max/min
Pa
150
Water volume
l
123
Water pressure max/min
bar
8/1
Max. water temperature (High limit thermostat)
ºC
100
Maximum temperature setpoint
ºC
90
Nominal water flow at dT=20K
m
3
/h
69.7
Hydraulic resistance at nominal water flow
kPa
175
Electrical connection
V
400
Frequency
Hz
50
Mains connection fuse
A
20
C25
IP class
-
IP20
Power consumption boiler (excl. pump)
W
2520
Power consumption 3-step pump (optional)
W
7500
Weight (empty)
kg
1665
Noise level at 1 meter distance
dB(A)
64
Ionisation current minimum
µA
6
PH value condensate
-
3.2
CE certification code
-
Water connections
-
DN80 PN16
Gas connection
-
DN80 PN16
Flue gas connection
mm
500
Air intake connection (for room sealed use)
mm
-
Condensate connection
mm