Before  operating  your  8XS,  please  read  the 
safety  instructions  in  the  User  Guide  on  the 
provided CD-ROM.

Detailed information can be found in the 

User Guide on the provided CD-ROM

Quick Start Guide

To read out the status of power outlets from your computer, enter the command 
as explained below:

Syntax of the command:

Rxy <ENTER>

Parameter     Value       Function

X                1 to 16     means the address of the Satellite (see table §1)
Y                1 to 8       indicates the number of the power outlet you want to control

The 8XS then sends the status of the specified power outlet using following syntax:
Pxy=z<CR><LF>
z = 0 if the power outlet is off
z = 1 if the power outlet is on
<CR> = Carriage Return
<LF>  = Line Feed

Examples:
Read out the status of the power outlet 5 of the Satellite with address 1:
R15   <ENTER> 
Read out the status of the power outlet 6 of the Satellite with address 2:
R26  <ENTER> 

RemarkThe 8XS accepts lower case and upper case commands.

L’ELECPS-8XS-EU

Satellite  is  a  power  distribution  and  control  unit  that  enables

power management of 8 devices through an RS-232 or RS-485 serial connection.

The number of controlled power outlets can be extended  up to  128 by cascading 
up to 16 Satellite models.

This 8XS is ideal to control power outlets through the serial connection of a PC, a 
KVM  switch  or  a  console  server.  It  can  also  be  connected  to  an  8XM  Master  to 
extend the number of controlled power outlets over IP. 

ELECDAN • 2 impasse de la noisette • 91370 VERRIERES-LE-BUISSON • FRANCE

Tél. +33 (0) 1 60 11 44 44 • Fax +33 (0) 1 69 20 39 63 • www.elecdan.com • sales@elecdan.com

Summary of Contents for ELECPS-8XS-EU

Page 1: ...iage Return LF Line Feed Examples Read out the status of the power outlet 5 of the Satellite with address 1 R15 ENTER Read out the status of the power outlet 6 of the Satellite with address 2 R26 ENTER Remark The 8XS accepts lower case and upper case commands L ELECPS 8XS EU Satellite is a power distribution and control unit that enables power management of 8 devices through an RS 232 or RS 485 se...

Page 2: ... outlets of the ELECPS 8XS EU can be individually controlled and the status of each power outlet can be read out using a simple ASCII protocol through a serial connection The connection can be done using the RS232 port SubD 9F connector marked RS232 on the front panel In this case use the supplied serial cable to connect the EPS to an available serial port of your PC using the RS485 port RJ45 conn...

Page 3: ...F z 1 si la prise est sous tension ON CR Carriage Return LF Line Feed Exemples Pour connaître l état de la prise secteur 5 de l EPS Satellite 1 R15 ENTER Pour connaître l état de la prise secteur 6 de l EPS Satellite 2 R26 ENTER Remarque l EPS Switch accepte les commandes en majuscules et minuscules L ELECPS 8XS EU Satellite est un système de contrôle et de distribution d alimentation qui permet d...

Page 4: ...être connu en utilisant un simple protocole ASCII via une connexion série La connexion peut être réalisée via le port RS232 connecteur série DB 9F sur la face avant Dans ce cas utilisez le câble série fourni pour connecter l EPS à un port série disponible de votre PC via le port RS485 connecteur RJ45 marqué xBus sur la face avant Dans ce cas il vous faut réaliser un câble série spécifique cf broch...

Reviews: