Control System
6 MINICHILLER CONTROL
4)
5)
If an alarm is occured, the alarm code is displayed, but
after 30', even if the alarm is still active, the display shows
again the mode but "Alar" message is displayed for 2'
every 10' when an alarm is active. When we enter in
Alarm list, the first alarm code displayed is the last
occurred.
Table 4
Alarms Table
Fault description
Fault
code
ADC
CPE
EPF
REF
CPNC
EPNC
EWTH
EWTL
LWTH
LWTL
OATH
OATL
OCTL
OCTH
HP
HPC
LP
LO
HI
Cl
CIH
DEIC
OFF
COOL
HEAT
FS
CF1
OF1
PF
LOu
CONF
CFC1
ADC error
Turn on the main switch of the power line.
1)
For an ideal heating of the oil in the compressor's crank-
case and for a proper removal of the refrigerant from the
oil, the operation described in sub-paragraph 1) above
should be performed several hours before the actual
start-up of the equipment.
2)
6.1.2 Starting and using the Unit
To properly use the unit in full safety, please read and under-
stand the instructions provided below.
1)
2)
3)
Table 3
Status display
Display Description
When compressor is operating
Compressor in heat mode
De-ice in operation
Off mode
Cool mode with no compressors on
Heat mode with no heating on
Not allowed configuration
Low water volume
PF input open, pump internal overload
OF1 input open, outdoor fan overload
CF1 input open, compressor 1 overload
High pressure cut-out
Condensing pressure transducer failure, out of range.
Condensing pressure transducer failure, no change error.
Evaporating pressure transducer failure, no change error.
Entering water temperature sensor short circuited
Entering water temperature sensor disconnected
Leaving water temperature sensor short circuited
Leaving water temperature sensor disconnected
Outdoor air temperature sensor short circuited
Coil temperature sensor disconnected
Outdoor air temperature sensor disconnected
Coil temperature sensor short circuited
High pressure protection, automatic reset for first three
times
Low pressure limit, unit cut out
Leaving water temperature below allowed limits
Entering water temperature is too high
Flow switch opens, low water flow
CP and EP no change,compressor not operating (burn out
or phase change).
Refrigerant leak - low pressures.
Evaporating pressure transducer failure, out of range.
6.1 Operating instructions
6.1.1 Before start-up
Before starting the equipment:
English
To start the unit,
close the remote switch according to
requirement, if display show OFF mode, press the right
button on display ^ for 5 seconds, please refer to the
wiredigram (see chapter 4.9). Break the connection the
unit willstop.
During the normal operation,if the connection between
No.6 and No. 7 terminal is closed, the unit will operate in
heating mode. When the connection is opened, the unit
wiu operate in cooling mode.
To modify the set-points,
press both ^ and > keys at the
same time for 5s, then the "OPEr" message appears on
the display. The parameters are scrolled using the ^
button and selected using the > button. When selected,
the values can be changed by using the ^ button to scroll
from the present value to max then min and can be
selected by pushing the > button. After selection the menu
will return to the beginning of the same parameter change
menu. If no button is pressed for 10s the display reverts
back to normal mode. Table 5 shows the list of standard
parameters.
During the normal operation the current value of entering
water temperature is displayed flashing alternatively with
the current status. To display other useful data, go to
level l, use the ^ button to scroll the menu, and use the >
button to select the display value. The display data are
shown is Table 6.
Summary of Contents for MQH 10T
Page 1: ...Zertifizierungsstelle Organismo Notificado No 0035 Библиотека СОК ...
Page 2: ...I X English ...
Page 42: ...VII Appendix A MQH 10T 12 14 16 18 C27019300 04 Factory Wired Field Wired Field Wired ...
Page 44: ...IX Appendix B Exploded View MQH 06 08M 08T ...
Page 45: ...X Appendix B MQH 10M 10T 12 14 16 18 ...
Page 46: ......
Page 47: ...Electra Air Conditioning shenzhen Co Ltd 2 Wuhe Avenue S Bantian Buji shenzhen China ...