PERFORMANCE DATA AND
PRESSURE CURVES
Service Manual – WMZ Revision Y05-01
5-33
5.25
WMZ17 GCZ17 R407C
5.25.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR WB/DB ID COIL (
°
C)
ENTERING AIR
DB OU COIL (
°
C)
DATA
15/21 17/24 19/27 21/29 23/32
TC
5.41
5.72
5.99
6.25
6.47
SC
3.50
3.71
3.91
3.82
3.89
15
(1)
PI
1.44
1.44
1.45
1.45
1.46
TC
5.35
5.67
5.94
6.20
6.41
SC
3.82
4.05
4.29
4.16
4.25
20
(1)
PI
1.56
1.57
1.57
1.58
1.59
TC
5.14
5.51
5.83
6.10
6.31
SC
3.40
3.64
3.85
3.79
3.88
25
PI
1.68
1.70
1.71
1.72
1.73
TC
4.82
5.19
5.62
5.83
6.04
SC
3.23
3.49
3.77
3.69
3.85
30
PI
1.82
1.84
1.87
1.88
1.89
TC
4.45
4.82
5.30
5.57
5.78
SC
3.04
3.31
3.62
3.58
3.72
35
PI
1.97
2.00
2.03
2.05
2.05
TC
4.03
4.40
4.88
5.14
5.35
SC
2.83
3.11
3.42
3.37
3.53
40
PI
2.12
2.15
2.19
2.21
2.23
TC
3.50
3.87
4.35
4.61
4.82
SC
2.57
2.85
3.21
3.15
3.30
46
PI
2.32
2.36
2.40
2.44
2.46
LEGEND
TC –
Total Cooling Capacity, kW
SC –
Sensible Capacity, kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Summary of Contents for WMZ Series
Page 19: ...4 2 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 3 GCZ 7 9 12 4 4 GCZ 17...
Page 20: ...4 3 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 5 GCZ 22...
Page 147: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 148: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 149: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 150: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...